Chapter 6 - Parameter Description [I/O]

[Current]

 

400V class -> 440V

FM terminal outputs inverter output current. The output

2.

Max DC link voltage : 200V class -> 400V

value is determined by,

 

400V class -> 800V

3.

Refer to chapter 2 Specification for inverter rated current.

FM Output Voltage = (Output current / Rated current) ×

 

 

10V × IO-41 / 150

 

 

[Voltage]

I/O-42: FDT (Frequency Detection) Level

I/O-43: FDT Bandwidth

 

 

 

 

FM terminal outputs inverter output voltage. The output

 

 

 

 

 

 

 

 

 

 

 

 

 

value is determined by,

 

 

 

 

 

 

 

 

 

 

 

I/O►

FDT freq

 

 

42

 

30.00

 

FM Output Voltage = (Output voltage / Max. output

 

 

 

 

 

voltage) × 10V × IO-41 / 100

 

42

30.00 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[DC link vtg]

 

Factory Default:

30.00 Hz

 

 

30.00

 

 

 

 

 

 

 

 

 

 

 

FM terminal outputs the DC link voltage of inverter. The

 

 

 

 

 

 

 

 

 

 

 

I/O►

FDT band

 

 

43

 

10.00

 

output value is determined by,

 

 

 

 

 

 

43

10.00 Hz

 

 

 

 

FM Output Voltage = (DC link voltage / Max. DC link

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

voltage) × 10V × IO-41 / 100

 

Factory Default:

10.00 Hz

 

 

10.00

 

 

 

These functions are used in I/O-44 [Multi-function Auxiliary

FM Terminal Output

Contact Output]. See [FDT-#] in I/O-44.

 

 

15Vpeak

Related Functions: I/O-44 [Multi-function Auxiliary Output]

 

Avg. 0~10V

I/O-44: Multi-function Auxiliary Contact Output

Time

define (AXA-AXC)

500Hz, 2msec (fixed)

 

[FM Output (FM-CM terminal)]

I/O► Aux mode

 

44

 

12

 

 

44

Run

 

 

 

 

 

 

 

 

 

[Torque]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

Run

 

 

 

12

 

FM terminal outputs the torque of inverter. The output

 

 

 

 

 

 

 

The auxiliary contact works (Close) when the defined

value is determined by

FM Output Voltage = (Torque current / Max.Torque

condition has occurred.

 

 

 

 

 

current) × 10V × IO-41 / 150

 

 

 

 

 

 

 

 

 

 

Setting Range

Description

FM-5G

 

 

LCD

7-Seg

 

 

Output frequency arrival detection

Output V

 

 

FDT-1

0

I/O-41 * 10 V

 

 

FDT-2

1

Specific frequency level detection

 

 

FDT-3

2

Frequency detection with pulse

10

 

 

FDT-4

3

Frequency detection with contact

 

 

closure

 

 

 

 

 

V

 

 

FDT-5

4

Frequency detection with contact

 

 

 

closure (inverted FDT-4)

 

 

 

 

 

 

 

 

OL

5

Overload detection

 

 

 

IOL

6

Inverter overload detection

0 %

100

I/O-40

Stall

7

Stall prevention mode detection

 

OV

8

Over voltage detection

 

 

 

 

 

LV

9

Low voltage detection

Note : 1. Max output voltage : 200V class -> 220V

 

OH

10

Overheat detection

 

 

 

 

6-44

Page 136
Image 136