Chapter 6 - Parameter Description [EXT]

EXT-54: Zero Speed Detection Level

EXT-55: Zero Speed Detection Bandwidth

Used to set the zero speed detection (SUB-B)

Only valid when FU2-39 [Control mode selection] is set to Vector_SPD, Vector_TRQ.

Detect the zero speed using I/O-44 [Multi-function auxiliary contact output selection]. Set Zspd Dect in I/O-44 [Multi-function auxiliary contact output] to activate this function.

Note : Sub-board is needed to use multi-function output terminal Q1,Q2,Q3.

Code

Keypad

Parameter

Factory

Setting

Display

Name

setting

range

 

EXT-

ZSD

Zero Speed

0.3[Hz]

0 – 120

Detection

54

Level

[Hz]

Level

 

EXT-

ZSD

Zero Speed

0.1[Hz]

0 – 0.3

Detection

55

Band

[Hz]

Bandwidth

 

Auxiliary contact relay activates as shown below if the following settings are applied to EXT-54 [Zero Speed Detection Level] and EXT-55 [Zero Speed Detection Bandwidth].

EXT-54

 

SPEED

 

 

EXT-54

ZSD

 

EXT-55

 

 

ZSD

Level

 

ZSD

 

 

Level

 

 

Band

 

 

 

AXA-

 

 

 

 

 

 

 

 

 

 

Close

 

Close

 

 

AXC

 

 

 

 

 

 

 

 

 

 

 

 

 

Related parameters : FU2-39 [Control mode selection] I/O-44 [Multi-function auxiliary contact output]

EXT-56: Torque Detection Level

EXT-57: Torque Detection Bandwidth

Use to set output torque detection (SUB-B)

Only valid when FU2-39 [Control mode selection] is set to Vector_SPD, Vector_TRQ.

Detect Torque using I/O-44 [Multi-function auxiliary contact output selection].

Note : Sub-board should be mounted to use multi- function output terminal Q1,Q2,Q3.

Code

Keypad

Description

Factory

Setting

Display

setting

range

 

 

 

 

Torque

 

 

EXT-56

TD Level

Detection

100[%]

0 – 150 [%]

 

 

Level

 

 

 

 

Torque

 

 

EXT-57

TD Band

Detection

5[%]

0 – 10 [%]

 

 

Bandwidth

 

 

EXT-56 [Torque Detection Level] and EXT-57 [Torque Detection Bandwidth] are activated in the following conditions as shown below.

 

TORQUE

 

EXT-56

EXT-57

EXT-56

TD Level

TD Band/

TD Level

 

2

 

AXA-

Close

 

AXC

 

 

 

Related parameters : FU2-39 [Control mode select] I/O-44 [Multi-function auxiliary contact output selection]

6-61