CHAPTER 6 - PARAMETER DESCRIPTION

6.1 Drive group [DRV]

DRV-00: Command Frequency or Command Torque/ Output Current (LCD)

DRV►

Cmd. Freq*

 

 

F *

 

0.00

00

0.00 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.00

Factory Default:

0.00 Hz

 

 

*In Torque mode : LCD display - Cmd. Trq 7 Segment - r

In FU2-39[Control Mode Selection], 4 (Sensorless_T) 6 (Vector_TRQ) is torque mode.

DRV-00 [Command Frequency or Command Torque] has two functions.

1)Digital frequency setting

-When DRV-04 [Frequency or Torque Mode] is set to 0 (KeyPad-1) or 1 (KeyPad-2), command freq is not settable above FU1-20 [Maximum Frequency].

2) Monitoring function setting

-Command frequency displayed during stop

-Output current/frequency displayed during run.

Analog/digital frequency command setting in DRV-04 [Frequency or Torque Mode]:

DRV-04 [Frequency or Torque Mode] is set to 2 (V1),3 (I) or 4 (V1+I), frequency command is set via I/O-01~10 [Analog Frequency command/Torque]. Refer to I/O-01~10 for detail description.

DRV-16 [Speed Unit Selection] is set to 1 (Rpm), speed is displayed in Rpm.

If FU2-39 is set to 4 (Sensorless_T) or 6

(Vector_TRQ), speed is displayed as the percent[%] to the rated torque. Torque command is settable in DRV-04 [Frequency or Torque Mode].

* Factory default setting = 100[%] (Up to 150[%] settable)

Setting the DRV-04 [Frequency or Torque Mode]

(Note: In torque mode, speed unit is automatically displayed in [%])

 

Setti

 

DRV-04

 

Parameter

 

Programming Description

 

ng

 

 

Name

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. In DRV-00, press the

 

 

 

KeyPad-

 

 

 

[PROG] key. 2. Enter the

 

0

 

 

 

 

desired freq. 3. Press the [ENT]

 

1

 

 

 

 

 

 

 

 

key to write the new value into

 

 

 

 

 

 

 

 

 

 

 

 

 

 

memory.

 

 

 

 

 

Digital freq.

 

1. In DRV-00, press the

 

 

 

 

 

command

 

[PROG] key. 2. Press the

 

 

 

KeyPad-

 

 

 

[ (Up)] or [ (Down)] key to

 

1

 

 

 

 

set the desired freq., while the

 

2

 

 

 

 

 

 

 

 

inverter keeps running. 3. Press

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the [ENT] key to write the new

 

 

 

 

 

 

 

value into memory.

 

 

 

 

 

 

 

Control terminal “V1” Voltage

 

 

 

 

 

 

 

analog input

 

2

 

V1

 

 

 

(0 to 0V)

 

 

 

 

 

 

 

See the description of I/O-

 

 

 

 

 

 

01~05.

 

 

 

 

 

Analog freq.

 

Control terminal “I” Current

 

 

 

 

 

 

analog input (4 to 20mA)

 

3

 

I

 

command

 

 

 

 

 

See the description of I/O-

 

 

 

 

 

 

 

 

 

 

 

 

 

06~10.

 

 

 

 

 

 

 

Control terminal “V1”+“I” (0-

 

4

 

V1+I

 

 

 

10V/4-20mA) Analog input

 

 

 

 

 

See the description of I/O-

 

 

 

 

 

 

 

 

 

 

 

 

 

01~10.

Command Freq/Torque setting via “V1” input terminal when set DRV-04 [Frequency/Torque mode] to 2 (V1) or 4 (V1+I)

Code

Default setting

Setting range

I/O-01

10 [msec]

0 ~ 10000 [msec]

I/O-02

0 [V]

0 ~ 10 [V]

I/O-03

0 [Hz]

0 ~ Max. freq

I/O-04

10 [V]

0 ~ 10 [V]

I/O-05

60 [Hz]

0 ~ Max freq

6-1