Chapter 8 - Troubleshooting & Maintenance

Keypad Display

Protective

Description

LCD

7-Segment

Function

 

Option (**)

OPT

Option Fault

Fault at the internal option of the inverter.

 

 

 

 

 

 

 

Inverter H/W

A fault signal is output when an error occurs to the control circuitry of the

HW-Diag

HW

inverter. There are the Wdog error, the EEP error, and the ADC Offset for this

Fault

 

 

fault

 

 

 

COM Error

Err

Communication

This fault is displayed when the inverter cannot communicate with the keypad.

CPU Error

Error

 

 

 

 

 

According to the I/O-48 [Operating Method when the Frequency Reference is

 

 

 

Lost] setting, there are three modes: continue operation, decelerate and stop,

LOP

LP

Operating Method

and free run,

LOR

LR

when the

LOP: Displayed when option frequency reference is lost (DPRAM time out)

LOV

LV

LOR: Displayed when option frequency reference is lost (Communication

Frequency

LOI

LI

network fault)

Reference is Lost

LOX

LX

 

LOV: Displayed when ‘V1’ analog frequency reference is lost.

 

 

 

LOI: Displayed when ‘I‘ analog frequency reference is lost.

 

 

 

LOX: Displayed when sun-board (V2, ENC) analog frequency reference is lost.

Inv. OLT

IOLT

Inverter Overload

The inverter turns off its output when the output current of the inverter flows

more than the rated level (150% for 1 minute, 200% for 0.5 seconds).

 

 

Thermal Sensor

Inverter uses NC thermal sensor for detecting heat sink temperature. If this

NTC open

NTC

message is displayed, the thermal sensor wire may be cut. (Inverter keeps

 

 

Opened

operating)

 

 

 

MC Fail

MCF

Magnetic

This fault is displayed when input power is not applied or M/C inside the inverter

contactor fault

becomes faulty.

 

 

To reset fault perform one of the following:

}Press RESET key on the keypad.

}Close RST-CM terminals.

}Cycle power to the inverter.

If a problem persists, please contact the factory or your local distributor.