Chapter 2 - Operation

2.2.1LCD Keypad Display

2) Run/Stop Source

3) Frequency Setting Source

1) Parameter group

4) Output Current

 

 

DRV¢ºT/K

0.0 A

 

 

 

00 STP

0.00 Hz

 

5) Parameter Code

7) Drive Output Frequency During Run,

 

 

 

 

 

 

6) Operating Status

Command Frequency During Stop

 

 

 

 

 

 

 

 

 

Displays

 

 

Description

 

1) Parameter Group

 

Displays the parameter group. There are DRV, FU1, FU2, I/O, EXT, COM, APP groups.

 

2) Run/Stop Source

 

Displays the source of motor Run and Stop

 

 

 

K: Run/Stop using FWD, REV buttons on keypad

 

 

 

T: Run/Stop using control terminal input FX, RX

 

 

 

O: Run/Stop via option board

 

 

3) Frequency Setting

 

Displays the source of command frequency setting

 

Source

 

K: Frequency setting using keypad

 

 

 

V: Frequency setting using V1 (0 ~10V) or V1 + I terminal

 

 

 

I: Frequency setting using I (4 ~ 20mA) terminal

 

 

 

U: Up terminal input when Up/Down operation is selected

 

 

 

D: Down terminal input when Up/Down operation is selected

 

 

 

S: Stop status when Up/Down operation is selected

 

 

 

O: Frequency setting via Option board

 

 

 

X: Frequency setting via Sub board

 

 

 

J: Jog terminal input

 

 

 

 

1 ~ 8: Step frequency operation

 

 

 

* During Auto operation, 2) and 3) display the ‘sequence number/step’.

 

4) Output Current

 

Displays the Output Current during operation.

 

5) Parameter Code

 

Displays the code of a group. Use the ▲(Up), ▼(Down) key to move through 0~99 codes.

 

6) Operating Status

 

Displays the operation information.

 

 

 

STP: Stop Status

 

 

 

 

FWD: During Forward operation

 

 

 

REV: During Reverse operation

 

 

 

DCB: During DC Braking

 

 

 

 

LOP: Loss of Reference from Option Board (DPRAM fault)

 

 

 

LOR: Loss of Reference from Option Board (Communication network fault)

 

 

 

LOV: Loss of Analog Frequency Reference (V1: 0~10V)

 

 

 

LOI: Loss of Analog Frequency Reference (I: 4~20mA)

 

 

 

LOS: Loss of Reference from Sub-Board

 

7) Drive Output Frequency

 

Displays the Output Frequency during run.

 

Command Frequency

 

Displays the Command Frequency during stop.

 

2-3

Page 31
Image 31
HP 30 30 manual Operation LCD Keypad Display, 00 Hz, Displays Description