Chapter 4 – Function Settings

Before selecting Vector control mode, encoder setting should be done as indicated above. If the parameter value of actual motor is set in common setting, execute Auto-tuning before selecting vector control mode.

Parameter Name

Code

Description

 

 

 

Control Mode Selection

FU2-39

Select Vector_SPD or Vector_TRQ

 

 

 

Forward/ Reverse

EXT-27, EXT-28

Setting the FWD/REV limit to the torque current

Torque Limit

 

 

 

P-Gain/ I-Gain for

EXT-25, EXT-26

Setting P/I Gain for Vector_SPD control

(Sensored) Vector_SPD

 

 

Speed Limit setting

EXT-50, EXT-51

Setting speed limit for Vector_TRQ

EXT-52, EXT-53

 

 

Zero Speed Detection

EXT-54, EXT-55

Setting on/off of Multi-function output terminal relay when

Level/ Bandwidth

the motor speed reaches to 0.

 

 

 

 

Torque Detection

EXT-56, EXT-57

Detect certain level/bandwidth of Torque

Level/Bandwidth

 

 

4.1.2Advanced function 1 setting

SV-ACtionMaster inverter features advanced function parameters to maximize efficiency and performance of the motor. It is recommended to use as factory setting unless parameter value change is necessary.

1) V/F control

Parameter Name

Code

Description

 

 

 

 

 

Use it according to load characteristics. If User V/F is

V/F Pattern

FU1-29

selected, User can select the optimum output V/F

characteristic for the aplication and load characteristics in

 

 

 

 

[FU1-30]~[FU1-37]

 

 

 

 

 

Used to output torque in an intended direction. Inverter

Dwell operation

FU2-07

stops acceleration for the preset [FU2-08] Dwell time

while running at Dwell frequency [FU2-07] and starts

FU2-08

 

acceleration at commanded frequency. Setting [FU2-08]

 

 

 

 

Dwell time to 0 disable the Dwell operation.

 

 

When it is desired to avoid resonance attributable to the

 

 

natural frequency of a mechanical system, these

 

FU2-10

parameters allow resonant frequencis to be jumped. Up to

Frequency jump

three areas can be set, with the jump frequencies set to

FU2-11~16

 

either the top or bottom point of each area. To enable the

 

 

 

 

function, set [FU2-10] to ‘Yes’ and set the value in [FU2-

 

 

11]~[ FU2-16].

S-shaped curve

FU2-17/ FU2-18

This pattern has an effect on the prevention of cargo

collapse on conveyor etc and reduction in an acceleration/

Accel/Decel pattern

 

deceleration shock.

 

 