Chapter 6 - Parameter Description [I/O]

I/O-21 ~ I/O-24: Step Frequency 4, 5, 6, 7

I/O►

Step freq-4

 

 

 

 

 

 

 

 

21

 

40.00

 

21

40.00 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

40.00 Hz

 

 

40.00

 

I/O►

Step freq-7

 

 

24

 

30.00

 

24

30.00 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

30.00 Hz

 

 

30.00

 

These codes set the step frequencies. These frequencies are applied when the multi-function input terminals (P1, P2, P3) select the step. See [Speed-L, Speed-M, Speed-H] in I/O-12 ~ I/O-14.

Related Functions: DRV-05 ~ DRV-07 [Step Frequency 1 ~ 3] I/O-12 ~ I/O-14 [Multi-function inputs] I/O-17 [Filtering Time Constant]

Output Frequency

 

 

 

 

 

Speed 3

 

 

 

 

 

 

Speed 2

 

 

 

 

 

 

Speed 1

 

 

 

 

 

 

Speed 0

 

 

 

 

 

 

 

 

 

 

 

 

Time

Speed 4

 

 

 

 

JOG

 

Speed 5

 

 

 

 

 

 

Speed 6

 

 

 

 

 

 

Speed 7

 

 

 

 

 

 

P1-CM

ON

ON

ON

ON

 

Time

 

 

 

 

 

 

P2-CM

 

ON

 

ON

 

Time

 

 

 

 

 

 

P3-CM

 

 

ON

 

Time

 

 

 

 

 

 

JOG-CM

 

 

 

 

ON

Time

 

 

 

 

 

 

FX-CM

ON

 

 

 

 

Time

 

 

 

 

 

 

RX-CM

 

 

 

ON

 

Time

 

 

 

 

 

 

 

[‘JOG’ and ‘Multi-Step’ Operation]

 

 

I/O-25 ~ I/O-38: 1st ~ 7th Accel/Decel Time

I/O►

Acc time-1

 

 

25

 

20.00

 

25

20.0 sec

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

20.0 sec

 

 

20.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I/O► Dec time-7

 

 

38

 

20

 

38

20.0 sec

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

20.0 sec

 

 

20.0

 

These codes are applied when the multi-function input terminals (P1, P2, P3) select the Accel/Decel time. See [XCEL-L, XCEL-M, XCEL-H] in I/O-12 ~ I/O-14.

Related Functions: DRV-01 ~ DRV-02 [Accel/Decel Time] FU2-70 [Reference Freq. for Accel/Decel] FU2-71 [Accel/Decel Time Scale] I/O-12 ~ I/O-14 [Multi-function inputs]

I/O-40: FM (Frequency Meter) Output

I/O-41: FM Adjustment

I/O►

FM mode

 

40

 

0

 

40

Frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

Frequency

0

 

 

 

 

 

 

 

I/O►

FM Adjust

 

41

 

100

 

41

 

100 %

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

100 %

 

 

100

 

Frequency meter displays the inverter output Frequency, Current, Voltage and DC link voltage with pulse signals on the FM terminal. The average ranges from 0V to 10V. I/O- 41 is used to adjust the FM value.

[Frequency]

FM terminal outputs inverter output frequency. The output value is determined by,

FM Output Voltage = (Output freq. / Max. freq.) × 10V × IO-41 / 100

6-43