Chapter 6 - Parameter Description [FU2]

FU2-51: PID Feedback Signal Selection

FU2-52: P Gain for PID Control

FU2-53: I Gain for PID Control

FU2-54: D Gain for PID Control

FU2-55: High Limit Frequency for PID Control

FU2-56: Low Limit Frequency for PID Control

FU2► PID F/B

 

 

51

 

0

 

51

I

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

 

I

0

 

Select the feedback signal for PID control. This can be set one of ‘I’, ‘V1’, ‘V2’ according to the signal (current or voltage) and the terminal (V1 or V2).

FU2►

PID P-gain

 

 

52

 

300.0

 

52

300.0 %

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

300.0 %

 

 

300.0

 

Set the proportional gain for PID control. When P-Gain is set at 100% and I-Gain at 0.0 second, it means the PID controller output is 100% for 100% error value.

FU2►

PID I-time

 

 

53

 

30.0

 

53

30.0 sec

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

30.0 sec

 

 

30.0

 

Set the integral gain for PID control. This is the time the PID controller takes to output 100% for 100% error value.

FU2► PID D-time

 

54

 

0.0

 

54

0.0 ms

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

0.0 ms

 

 

0.0

 

Set the differential gain for PID control.

FU2►

PID +limit

 

 

55

 

60.00

 

55

60.00 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

60.00 Hz

 

 

60.00

 

This is the frequency at which the output frequency is limited under during PID control.

FU2►

PID -limit

 

 

56

 

60.00

 

56

60.00 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

60.00 Hz

 

 

60.00

 

This is the frequency at which the output frequency is limited over during PID control.

FU2-57: PID Output Inversion

FU2-58: PID Output Scale

FU2-59: PID P2 Gain

FU2-60: P Gain Scale

FU2►PID Out Inv.

 

57

 

0

 

57 ---

No ---

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

No

 

 

 

0

 

This code is used to inverter PID controller output.

FU2►PID OutScale

 

 

58

 

100.0

 

58

100.0 %

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

100.0 %

 

 

100.0

 

This code sets the scale of PID controller output.

FU2► PID P2-gain

 

 

59

 

100.0

 

59

100.0 %

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

100.0 %

 

 

100.0

 

This code sets the second P-Gain for PID control. The second P-Gain is can be selected for PID controller by setting a multi-function input (I/O-12 ~ I/O14 or EXT-02 ~ EXT-04) to ‘Open-loop’.

FU2►P-gain Scale

 

 

60

 

100.0

 

60

100.0 %

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

100.0 %

 

 

100.0

 

This code sets the scale of P-Gain and P2-Gain. (FU2-52, FU2-59)

PID output value can be set to ‘0’ by setting a multi- function input terminal (P1 ~ P6) to ‘Open loop’ in I/O- 12 ~ I/O-14 or EXT-02 ~ EXT-04.

The accumulated value by I-Gain can be set to ‘0’ by setting a multi-function input terminal (P1 ~ P6) to ‘iTerm Clear’ in I/O-12 ~ I/O-14 or EXT-02 ~ EXT-04.