Chapter 5 - Parameter List

Code

Description

Keypad Display

Setting Range

 

Units

Factory

Adj.

Page

LCD

 

7-Segment

LCD

 

7-Segment

Default

During

 

 

 

 

 

Run

 

FU2-72

Power On Display

PowerOn disp

72

0 to 12

 

 

1

0

Yes

6-2

 

 

 

 

 

 

 

 

 

 

 

 

FU2-73

User Display Selection

User disp

73

Voltage

 

0

-

Voltage

Yes

6-2

Watt

 

1

 

 

 

 

 

 

 

 

 

 

FU2-74

Gain for Motor Speed

RPM factor

74

1 to 1000 [%]

 

1

100 [%]

Yes

6-2

Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DB (Dynamic Braking)

 

 

 

None

 

0

 

 

 

 

FU2-75

DB mode

75

Int. DB-R

 

1

-

Int. DB-R

Yes

6-2

Resistor Mode Selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ext. DB-R

 

2

 

 

 

 

FU2-7623

Duty of Dynamic Braking

DB %ED

76

0 to 30 [%]

 

1

10 [%]

Yes

6-2

 

Resistor

 

 

 

 

 

 

 

 

 

 

 

FU2-79

Software Version

S/W version

79

Ver 2.0

 

 

-

-

-

6-2

FU2-8124

2nd Acceleration Time

2nd Acc time

81

0 to 6000 [sec]

 

0.1

5.0 [sec]

Yes

 

FU2-82

2nd Deceleration Time

2nd Dec time

82

0 to 6000 [sec]

 

0.1

10.0 [sec]

Yes

 

FU2-83

2nd Base Frequency

2nd BaseFreq

83

30 to FU1-20

 

0.01

60.00 [Hz]

No

 

 

 

 

 

 

Linear

 

0

 

 

 

 

FU2-84

2nd V/F Pattern

2nd V/F

84

Square

 

1

-

Linear

No

 

 

 

 

 

 

User V/F

 

2

 

 

 

 

FU2-85

2nd Forward Torque Boost

2nd F-boost

85

0 to 15 [%]

 

0.1

2.0 [%]

No

 

FU2-86

2nd Reverse Torque

2nd R-boost

86

0 to 15 [%]

 

0.1

2.0 [%]

No

6-2

Boost

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FU2-87

2nd Stall Prevention Level

2nd Stall

87

30 to 150 [%]

 

1

150[ %]

No

 

FU2-88

2nd Electronic Thermal

2nd ETH 1min

88

FU2-89 to 200 [%]

 

1

150 [%]

Yes

 

Level for 1 minute

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FU2-89

2nd Electronic Thermal

2nd ETH cont

89

50 to FU2-88

 

1

100 [%]

Yes

 

Level for continuous

(Maximum 150%)

 

 

 

 

 

 

 

 

 

FU2-90

2nd Rated Motor Current

2nd R-Curr

90

1 to 200 [A]

 

0.1

3.6 [A]

No

 

FU2-91

Read Parameters into

Para. Read

91

No

 

0

-

No

No

 

Keypad from Inverter

Yes

 

1

 

 

 

6-2

FU2-92

Write Parameters to

Para. Write

92

No

 

0

-

No

No

 

 

Inverter from Keypad

Yes

 

1

 

 

 

 

 

 

 

 

 

No

 

0

 

 

 

 

 

 

 

 

 

All Groups

 

1

 

 

 

 

 

 

 

 

 

DRV

 

2

 

 

 

 

 

 

 

 

 

FU1

 

3

 

 

 

 

FU2-93

Initialize Parameters

Para. Init

93

FU2

 

4

-

No

No

6-2

 

 

 

 

 

I/O

 

5

 

 

 

 

 

 

 

 

 

EXT

 

6

 

 

 

 

 

 

 

 

 

COM

 

7

 

 

 

 

 

 

 

 

 

APP

 

8

 

 

 

 

23Code FU2-76 appears only when FU2-75 is set to ‘Ext. DB-R’.

24Code FU2-81 through FU2-90 appear only when one of I/O-12 ~ I/O-14 is set to ‘2nd function’.

5-9

Page 69
Image 69
HP 30 30 manual RPM factor, DB mode, Version, Para. Read, Para. Write, Para. Init