Chapter 6 - Parameter Description [DRV]

DRV-02: Deceleration Time

DRV►

Dec. time

 

 

 

 

 

 

 

 

02

 

20.0

 

02

20.0 sec

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

20.0 sec

 

 

20.0

 

 

 

 

 

 

 

 

 

 

The inverter targets the FU2-70 when accelerating or decelerating. When the FU2-70 is set to “Maximum Frequency”, the acceleration time is the time taken by the motor to reach FU1-20 from 0 Hz. The deceleration time is the time taken by the motor to reach 0 Hz from FU1-20 [Maximum Frequency].

When the FU2-70 is set to ‘Delta Frequency’, the acceleration and deceleration time is the time taken to reach a targeted frequency (instead the maximum frequency) from a frequency.

The acceleration and deceleration time can be changed to a preset transient time via multi-function inputs. By setting the multi-function inputs (P1, P2, P3) to ‘XCEL-L’, ‘XCEL- M’, ‘XCEL-H’ respectively, the Accel and Decel time set in I/O-25 to I/O-38 are applied according to the binary inputs of the P1, P2, P3.

Output Frequency

Max. Freq.

 

 

Time

Acc. time

Dec. time

Related Functions: FU1-20 [Max freq]

FU2-70 [Reference freq. for Accel/Decel] FU2-71 [Accel/Decel time scale] I/O-12 to I/O-14 [Multi-function input terminal P1, P2, P3]

I/O-25 to I/O-38 [Acc/Dec time for step frequency]

FU2-70: Selects the frequency to be targeted for acceleration and deceleration. [Max Freq, Delta Freq]

FU2-71: Selects the time scale. [0.01, 0.2, 1]

I/O-12 to I/O-14: Sets the terminal function of P1, P2, P3 terminal inputs.

I/O-25 to I/O-38: Presets the Accel/Decel time activated via multifunction inputs (P1, P2, P3)

Note: I/O-12 to I/O-14: Sets the terminal function of P1, P2, P3 terminal inputs.

 

Code

 

LCD

 

Description

 

XCEL-

 

XCEL-

 

XCEL-

 

Factory

 

 

display

 

 

H

 

M

 

L

 

setting

 

 

 

 

 

 

 

 

 

 

DRV-

 

Acc time

 

Acc time 0

0

0

0

 

10 sec

 

01

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DRV-

 

Dec time

 

Dec time 0

0

0

0

 

20 sec

 

02

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I/O-25

ACC-1

 

Acc time 1

0

0

1

 

20 sec

 

I/O-26

DEC-1

 

Dec time 1

0

0

1

 

20 sec

 

I/O-27

ACC-2

 

Acc time 2

0

1

0

 

30 sec

 

I/O-28

DEC-2

 

Dec time 2

0

1

0

 

30 sec

 

I/O-29

ACC-3

 

Acc time 3

0

1

1

 

40 sec

 

I/O-30

DEC-3

 

Dec time 3

0

1

1

 

40 sec

 

I/O-31

ACC-4

 

Acc time 4

1

0

0

 

50 sec

 

I/O-32

DEC-4

 

Dec time 4

1

0

0

 

50 sec

 

I/O-33

ACC-5

 

Acc time 5

1

0

1

 

40 sec

 

I/O-34

DEC-5

 

Dec time 5

1

0

1

 

40 sec

 

I/O-35

ACC-6

 

Acc time 6

1

1

0

 

30 sec

 

I/O-36

DEC-6

 

Dec time 6

1

1

0

 

30 sec

 

I/O-37

ACC-7

 

Acc time 7

1

1

1

 

20 sec

 

I/O-38

DEC-7

 

Dec time 7

1

1

1

 

20 sec

FU2-71 [Accel/Decel time scale]

Set the Accel / Decel time unit.

 

Setting

 

Unit

 

Description

 

0

 

0.01 sec

 

Minimum 0 sec settable

 

 

 

Maximum 60 sec settable

 

 

 

 

 

Minimum 0 sec settable

 

1

 

0.1 sec

 

Maximum 600 sec settable

 

 

 

 

 

(Factory setting)

 

2

 

1 sec

 

Minimum 0 sec settable

 

 

 

Maximum 6000 sec settable*

 

 

 

 

 

* Up to 6000 sec setting is avaiable via LE-200 keypad.

DRV-03: Drive Mode (Run/Stop Method)

DRV►

Drive mode

 

 

03

 

1

 

03

Keypad

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

Fx/Rx-1

 

 

1

 

 

 

 

 

 

 

 

 

 

Select the source of run/stop command.

6-3

Page 87
Image 87
HP 30 30 manual DRV-02 Deceleration Time, 20.0, DRV-03 Drive Mode Run/Stop Method