Chapter 1 - Installation

Wires and Terminal Lugs

Refer to the following table for wires, terminal lugs, and screws used to connect the inverter power input (R, S, T) and output (U, V, W).

 

Inverter Capacity

 

 

Terminal

 

 

Screw

 

 

Ring Terminals

 

 

 

 

 

Wire9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Screw Size

 

 

Torque8

 

 

 

 

 

 

 

 

 

mm²

 

 

 

AWG

 

 

 

 

 

 

 

 

(Kgf·cm)/lb-in

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R,S,T

 

 

U,V,W

 

 

R,S,T

 

 

U,V,W

 

 

R,S,T

 

 

U,V,W

 

 

 

1 ~ 3 HP

 

 

M3.5

 

15 / 10

 

 

2-4

 

2-4

 

 

2

 

2

 

 

14

 

14

 

 

 

5 HP

 

 

M3.5

 

15 / 10

 

 

2-4

 

2-4

 

 

3.5

 

3.5

 

 

12

 

12

 

 

 

7.5 HP

 

 

M4

 

15 / 10

 

 

5.5-5

 

5.5-5

 

 

5.5

 

5.5

 

 

10

 

10

 

 

200V

10 HP

 

 

M4

 

15 / 10

 

 

14-5

 

8-5

 

 

14

 

8

 

 

6

 

8

 

 

Class

15 HP

 

 

M5

 

26 / 18

 

 

14-5

 

14-5

 

 

14

 

14

 

 

6

 

6

 

 

 

20 HP

 

 

M5

 

26 / 18

 

 

22-6

 

22-6

 

 

22

 

22

 

 

4

 

4

 

 

 

25 HP

 

 

M6

 

45 / 31

 

 

38-8

 

38-8

 

 

30

 

30

 

 

2

 

2

 

 

 

30 HP

 

 

M6

 

45 / 31

 

 

38-8

 

38-8

 

 

38

 

30

 

 

2

 

2

 

 

 

1 ~ 5 HP

 

 

M3.5

 

15 / 10

 

 

2-4

 

2-4

 

 

2

 

2

 

 

14

 

14

 

 

 

7.5 HP

 

 

M4

 

15 / 10

 

 

5.5-5

 

5.5-5

 

 

3.5

 

2

 

 

12

 

14

 

 

400V

10 HP

 

 

M4

 

15 / 10

 

 

14-5

 

8-5

 

 

3.5

 

3.5

 

 

12

 

12

 

 

15 HP

 

 

M5

 

26 / 18

 

 

14-5

 

14-5

 

 

5.5

 

5.5

 

 

10

 

10

 

 

Class

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20 HP

 

 

M5

 

26 / 18

 

 

22-6

 

22-6

 

 

14

 

8

 

 

6

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25 HP

 

 

M6

 

45 / 31

 

 

38-8

 

38-8

 

 

14

 

8

 

 

6

 

8

 

 

 

30 HP

 

 

M6

 

45 / 31

 

 

38-8

 

38-8

 

 

22

 

14

 

 

4

 

6

 

Power and Motor Connection

R

S

T

G N B1 B2 U

V

W

3 Phase

Power Input

Power supply must be connected to the R, S, and T terminals.

Connecting it to the U, V, and W terminals causes internal damages to the inverter. Arranging the phase sequence is not necessary.

Motor

Motor should be connected to the U, V, and W terminals.

If the forward command (FX) is on, the motor should rotate counter clockwise when viewed from the load side of the motor. If the motor rotates in the reverse, switch the U and V terminals.

8Apply the rated torque to terminal screws. Loose screws can cause of short circuit or malfunction. Tightening the screws too much can damage the terminals and cause a short circuit or malfunction.

9Use copper wires only with 600V, 75ratings.

1-12