Chapter 6 - Parameter Description [FU2]

Note: When the reference frequency is set inside the jump frequency, the output frequency goes to the frequency marked by “n” symbol.

Note: If one frequency jump range is required, set all ranges to the same range.

FU2-17: Start Curve for S-Curve Accel/Decel Pattern

FU2-18: End Curve for S-Curve Accel/Decel Pattern

FU2► Start Curve

 

17

 

40

 

17

40

%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

40%

 

 

 

40

 

 

 

 

 

 

 

 

 

 

 

 

 

FU2► End Curve

%

 

18

 

40

 

18

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

40%

 

 

 

40

 

 

 

 

 

 

 

 

 

This parameter is used to adjust the Accel and Decel pattern when ‘S-Curve’ is selected in FU1-05 and FU1-06 respectively. To use this function, the Reference Frequency for Accel and Decel set in FU2-70 should be set to ‘Delta freq’.

Output Frequency

 

 

 

Max. Freq./2

FU2-17

FU2-18

FU2-17

Time

FU2-18

 

Linear

 

Linear

[S0Curve Adjustment]

Actual Accel Time = DRV-01 + (DRV-01 * FU2-17)/2 + (DRV-01*FU2-18)/2

Actual Decel Time = DRV-02 + (DRV-02 * FU2-17)/2 + (DRV-02*FU2-18)/2

Ex) If DRV-10: 1 sec, FU2-17: 40%, FU2-18: 20%, Actual Accel Time = 1 sec + (1sec*0.4)/2 + (1sec*0.2)/2 = 1.3 sec

FU2-19: Input/Output Phase Loss Protection (Bit Set)

FU2► Trip select

 

19

 

00

 

19

00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

00

 

 

 

00

 

 

 

 

 

 

 

 

This function is used to cut the inverter output off in case of phase loss in either input power or inverter output.

FU2-19 [Phase Loss Protection Select]

 

Setting Range

FU2-19

Description

 

2nd bit

1st bit

 

 

 

 

 

0

0

00

Phase loss protection does not work

 

0

1

01

Protect inverter from output phase loss

 

1

0

10

Protect inverter from input phase loss

 

1

1

11

Protect inverter from input and output

 

phase loss

 

 

 

 

 

 

Related Functions: FU2-22 to FU2-25 [Speed Search]

 

FU2-20: Power ON Start Selection

FU2►Power-on run

 

20

 

0

 

20 --- No ---

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

No

 

 

 

0

 

 

 

 

 

 

 

 

If FUN-20 is set to ‘No’, restart the inverter by cycling the FX or RX terminal to CM terminal after power has been restored.

If FUN-20 is set to ‘Yes’, the inverter will restart after power is restored. If the motor is rotating by inertia at the time power is restored, the inverter may trip. To avoid this trip, use ‘Speed Search’ function by setting FU2-22 to ‘1xxx’.

6-17

Page 109
Image 109
HP 30 30 manual FU2-19 Input/Output Phase Loss Protection Bit Set, FU2-20 Power on Start Selection