Chapter 6 - Parameter Description [FU2]

FU2-69: Accel/Decel Change Frequency

FU2►Acc/Dec ch F

 

 

69

 

0

 

69

0.00 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

0.00 Hz

 

 

0

 

This function is used to change Accel/Decel ramp at a certain frequency. This is useful in textile machine application.

Note: If the multi-function input terminal (I/O-12 ~ I/O-14) is set to ‘XCEL-L’, XCEL-M’, or XCEL-H’, The Multi- Accel/Decel Time (I/O-25 ~ I/O-38) has the priority.

Max. Frequency

Accel/Decel

Output Frequency

Change

 

Frequency

DRV-01

[AccTime]

 

DRV-02 [DecTime]

 

 

 

 

I/O-25

[Acc Time1]

 

I/O-26 [Dec Time1]

FX

[Accel/Decel Change Operation]

FU2-70: Reference Frequency for Accel/Decel

FU2►Acc/Dec freq

 

 

70

 

0

 

70

Max freq

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

Max freq

 

 

0

 

This is the reference frequency for acceleration and deceleration. If a decided Accel/Decel time from a frequency to a target frequency is required, set this value to ‘Delta freq’.

Setting Range

Description

LCD

7-Seg

 

Max freq

 

The Accel/Decel time is the time that

0

takes to reach the maximum

 

 

frequency from 0 Hz.

 

 

 

The Accel/Decel time is the time that

 

 

Delta freq

1

takes to reach a target frequency

 

 

from a frequency (currently operating

 

 

 

 

 

 

 

 

frequency).

 

 

 

 

Related Functions: DRV-01, DRV-02 [Accel/Decel Time]

 

 

FU2-71 [Accel/Decel Time Scale]

 

 

I/O-25 ~ I/O-38 [1st ~ 7th Accel/Decel Time]

 

 

 

 

 

FU2-71: Accel/Decel Time Scale

FU2►

Time scale

 

 

71

 

0.1

 

71

0.1 sec

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

0.1 sec

 

 

0.1

 

This is used to change the time scale.

Related Functions: DRV-01, DRV-02 [Accel/Decel Time]

 

 

 

 

FU2-70 [Reference Freq. for Accel/Decel]

 

 

 

 

I/O-25 ~ I/O-38 [1st ~ 7th Accel/Decel Time]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting Range

 

 

 

Description

 

 

 

 

 

 

LCD

 

7-Seg

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.01 sec

 

 

The Accel/Decel time is changed by 0.01

 

 

 

0

second. The maximum setting range is

 

 

 

 

 

600 seconds.

 

 

 

 

 

 

0.1 sec

 

 

The Accel/Decel time is changed by 0.1

 

 

 

1

second. The maximum setting range is

 

 

 

 

 

6000 seconds.

 

 

 

 

 

 

1 sec

 

 

The Accel/Decel time is changed by 1

 

 

 

2

second. The maximum setting range is

 

 

 

 

 

60000 seconds.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FU2-72: Power On Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FU2►PowerOn disp

 

 

72

 

 

0

 

 

 

72

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

0

 

 

 

 

 

 

0

 

 

 

This code selects the parameter to be displayed first on keypad (DRV-00) when the power is turned on.

Setting

 

Description

Range

 

 

 

0

DRV-00

[Command Frequency]

1

DRV-01

[Acceleration Time]

2

DRV-02

[Deceleration Time]

3

DRV-03

[Drive Mode]

6-30

Page 122
Image 122