Chapter 6 - Parameter Description [DRV]

Related Functions: I/O-12 to I/O-14 [Reference Inputs] I/O-17 [Filtering Time Constant] I/O-21 to I/O-21 [Step Frequency 4~7]

I/O-01 to I/O-10: Scaling the analog input signals (V1 and I) for frequency reference.

I/O-17: Adjusts the response sensibility of the input terminal to eliminate contact noise.

I/O-21 to I/O-24: Sets the step frequency from 4 to 7.

Note: The frequency setting method of ‘Speed 0’ is decided by DRV-04.

DRV-08: Output Current

DRV►

Current

 

 

08

 

0.0

 

08

0.0 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

0.0 A

 

 

0.0

 

 

 

 

 

 

 

 

 

This code displays the output current of the inverter in RMS.

DRV-09: Motor Speed

DRV► Speed

 

 

09

 

0

09

0rpm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

0rmp

 

 

 

0

 

 

 

 

 

 

This code displays the motor speed in RPM while the motor is running.

Use the following equation to scale the mechanical speed using FU2-74 [Gain for Motor Speed display] if you want to change the motor speed display to rotation speed (r/min) or mechanical speed (m/min).

Motor speed = 120 * (F/P) * FU2-74

Where, F= Output Frequency and P= the Number of Motor Poles

DRV-10: DC Link Voltage

DRV►

DC link vtg

 

10

 

----

 

10

----- V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

---- V

 

 

----

 

 

 

 

 

 

 

 

 

This code displays the DC link voltage inside the inverter.

DRV-11: User Display Selection

DRV► User disp

 

11

 

0.0

 

11 Out

0.0 V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

0.0 V

 

 

0.0

 

 

 

 

 

 

 

 

This code displays the parameter selected in FU2-73 [User Display]. There are types of parameters in FU2-73: Voltage, Watt and Torque.

DRV-12: Fault Display

DRV►

Fault

 

 

12

 

nOn

 

12

None

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

None

nOn

 

 

 

 

 

 

 

 

 

This code displays the current fault (trip) status of the inverter. Use the PROG, ▲ and ▼ key before pressing the RESET key to check the fault content(s), output frequency, output current, and whether the inverter was accelerating, decelerating, or in constant speed at the time of the fault occurred. Press the ENT key to exit. The fault content will be stored in FU2-01 to FU2-05 when the RESET key is pressed. For more detail, please refer to Chapter 7.

[Fault Contents]

Fault (Trip)

Keypad display

LCD

7-Segment

 

Over-Current 1

Over Current 1

OC

Over-Voltage

Over Voltage

OV

External Trip Input A

External-A

EXTA

Emergency Stop

BX

BX

(Not Latched)

Low-Voltage

Low Voltage

LV

Fuse Open

Fuse Open

FUSE

Ground Fault

Ground Fault

GF

Over-Heat on Heat sink

Over Heat

OH

Electronic Thermal Trip

E-Thermal

ETH

Over-Load Trip

Over Load

OLT

Inverter H/W Fault

 

 

- EEP Error

HW-Diag

 

- ADC Offset

HW

- WDOG Error

 

 

- In-Phase Open

 

 

External Trip Input B

External-B

EXTB

Over-Current 2

Arm Short

ASHT

Option Error

Option

OPT

6-6