Jog

 

Jog Operation

 

 

Auto Operation

Operates via Internal Sequence by Setting Multi-Function Terminal (5 Way * 8 Step)

 

 

Fault Reset

Trip Status is Removed when Protection Function is Activated

 

 

Operating Status

Frequency Detection Level, Overload Alarm, Stalling, Over Voltage, Under Voltage, Inverter

 

Sig.

 

 

 

Overheating, Running, Stop, Constant Speed, Inverter By-Pass, Speed Searching, Auto-Operation

 

 

 

 

Step, Auto-Operation Sequence

 

Output

 

 

 

 

Fault Output

Contact Output (30A, 30C, 30B) – AC 250V 1A, DC 30V 1A

 

Indicator(FM,LM)

Choose 1 from Output Frequency, Output Current, Output Voltage, DC Voltage, Output Torque

 

 

 

 

 

 

 

Output Voltage: 0 ~ 10V (for FM: Linear output, 15V Max., LM), Pulse output: 500Hz (for LM).

 

Operation Function

DC Braking, Frequency Limit, Frequency Jump, Second Function, Slip Compensation, Reverse

 

 

 

 

 

Rotation Prevention, Auto Restart, Inverter By-Pass, Auto-Tuning, PID Control

Function

Inverter Trip

Over Voltage, Under Voltage, Over Current, Fuse Open, Ground Fault, Inverter Overheating, Motor

 

 

 

 

Overheating, Output Phase Open,

 

 

 

 

Overload Protection, External Fault 1, 2, Communication Error, Loss of Speed Command, Hardware

 

 

 

 

Fault, Option Fault etc.

Protective

 

 

 

 

Inverter Alarm

Stall Prevention, Overload Alarm, Temperature Sensor Fault

Momentary Power Loss

Less than 15msec: Continuous Operation,

 

 

 

 

 

More than 15msec: Auto Restart Possible

Display

 

 

 

Operation

Output Frequency, Output Current, Output Voltage, Frequency Value Setting, Operating Speed, DC

Keypad

 

Information

Voltage, Output Torque

 

Trip

Indicates a Fault when the Protection Function activates, Retains Up to 5 Faults

 

 

 

 

 

 

 

Information

 

 

Ambient Temperature

-10°C ~ 40 °C (14 °F ~ 104 °F), CE Certification: 41 °F ~ 104 °F (5 °C ~ 40 °C)

Environment

Storage Temperature

-20 °C ~ 65 °C (-4 °F ~ 149 °F)

Ambient Humidity

Less Than 90 % RH Max. (Non-Condensing), CE Certification: 5 ~85% (Non-Condensing)

Altitude - Vibration

Below 1,000m or 3,300ft above sea level · Below 5.9m/sec2 (=0.6g)

Air Pressure

86 ~ 106kPa

 

 

Application Site

No Corrosive Gas, Combustible Gas, Oil Mist, or Dust

Cooling Method

 

Forced Air Cooling

iii

Page 11
Image 11
HP 30 30 manual Iii