HP 30 30 manual Xcel stop Hold step, Gain2, Seq-L, Seq-M, Seq-H, Manual, Go step

Models: 30 30

1 218
Download 218 pages 18.86 Kb
Page 133
Image 133

 

 

 

 

 

 

Chapter 6 - Parameter Description [I/O]

[XCEL stop]

 

 

 

 

[Hold step]

 

 

 

 

 

Inverter stops accelerating and decelerating when this

This is used to hold the last step frequency in Auto-A

terminal is ON.

 

 

 

 

operation.

 

 

 

 

 

[P Gain2]

 

 

 

 

Related Functions: I/O-51 ~ I/O-84 [Sequence Operation]

 

 

 

 

 

 

 

 

 

 

This function is used to change P-Gain during PID

 

Output Frequency

 

 

 

 

operation. When this terminal is ON, PID controller

 

 

 

 

 

changes P-Gain with PID P2-Gian set in FU2-59.

 

Sequence 1

Sequence 3

 

Sequence 2

Refer to PID Control Block Diagram.

 

 

SEQ1 / 2F

 

 

 

 

 

[SEQ-L, SEQ-M, SEQ-H]

 

 

 

SEQ2 / 2F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

These functions are used for Auto drive (I/O-50).

 

SEQ1 / 1F

 

 

 

 

 

Five different sequences can be selected according to the

 

 

 

 

 

Time

combination of these terminals. Eight step frequencies,

SEQ3 / 2F

 

 

 

 

 

Accel/Decel time and steady speed time can be set for

 

 

 

 

 

 

each sequence. The following table shows the sequence

SEQ3 / 1F

 

 

 

 

 

of selection.

 

 

 

 

 

 

 

 

 

 

Step

Parameter

Speed-H

Speed-M

Speed-L

P1-CM

ON

 

 

 

 

‘SEQ-L’

 

 

 

Time

Frequency

Code

(P3)

(P2)

(P1)

 

 

 

 

 

P2-CM

 

 

 

 

 

Sequence 1

 

0

0

1

 

 

ON

 

 

 

‘SEQ-M’

 

 

 

Time

Sequence 2

 

0

1

0

 

 

 

 

I/O-50 ~

P3-CM

 

 

 

 

 

Sequence 3

1

0

0

 

 

 

 

 

I/O-84

‘Go step’ ON

ON

ON

ON

ON

Time

Sequence 4

0

1

1

 

 

 

 

 

 

 

Sequence 5

 

1

0

1

 

 

Minimum 100msec

 

0: OFF, 1: ON

 

 

 

 

 

 

 

 

 

 

 

 

[‘Go step’ in Auto-B Operation]

 

 

 

 

 

 

 

 

Note: The inverter stops after finishing all steps of that

sequence once the Auto (Sequence) operation is started.

Output Frequency

 

 

To stop the inverter during sequence operation, use ‘BX’

 

 

 

Sequence 1

Sequence 2

 

terminal on the control terminal strip.

 

 

SEQ2 / 2F

 

 

 

 

 

 

 

Related Functions: I/O-51 ~ I/O-84 [Sequence Operation]

SEQ1 / 2F

 

 

 

 

SEQ2 / 1F

 

 

 

 

SEQ1 / 1F

 

 

 

[Manual]

 

 

 

Time

This is used to exchange the operation mode of inverter

 

 

 

 

 

 

 

from Auto (Sequence) to manual operation.

 

 

 

 

DRV-03 [Drive Mode] and DRV-04 [Frequency Mode] are

P1-CM

 

 

 

applied when the mode has been changed.

ON

 

 

‘SEQ-L’

 

Time

 

 

 

 

Note: This function can be used only when the inverter is

P2-CM

 

ON

 

‘SEQ-M’

 

Time

stopped.

 

 

P3-CM

 

 

 

 

 

ON

 

[Go step]

‘Hold step’

 

Time

 

 

 

This is used to trigger the next step in a sequence of Auto-

 

[‘Hold step’ in Auto-A Operation]

 

B operation.

 

 

Related Functions: I/O-51 ~ I/O-84 [Sequence Operation]

 

 

 

 

6-41

Page 133
Image 133
HP 30 30 manual Xcel stop Hold step, Gain2, Seq-L, Seq-M, Seq-H, Manual, Go step