Chapter 6 - Parameter Description [DRV]

Output Phase Loss

Phase Open

PO

Inverter Over-Load

Inv. OLT

IOLT

Note: There are WDOG error, EEP error, and ADC Offset for the inverter Hardware Fault - the inverter will not reset when H/W fault occurs. Repair the fault before turning on the power.

Note: Only the highest-level fault will be displayed when multiple faults occur.

Related Functions: FU2-01 to FU2-05 [Previous Fault History] FU2-06 [Erase Fault History]

FU2-01 to FU2-05: There are up to 5 faults saved.

FU2-06: Erases the faults saved in FU2-01 to FU2-05.

DRV-13: Motor Direction Set (7-Segment Keypad)

130

Factory Default:

0

 

 

This code sets the motor direction when using the 7- Segment keypad.

7-Segment Display

Description

0

Run to forward direction

1

Run to reverse direction

DRV-14: Command/Output Frequency Display (LCD Keypad)

DRV►TAR 0.00Hz

14 OUT 0.00Hz

Factory Default:

0.00Hz

This code shows the Command (Target) Frequency set in DRV00 and inverter Output Frequency.

DRV-15: Reference/Feedback Frequency Display (LCD Keypad)

DRV►REF 0.00Hz

15 FBK 0.00Hz

Factory Default:

0.00Hz

 

 

This code shows the Reference Frequency and Feedback Frequency while PID operation.

This code appears only when ‘PID’ is selected in FU2-47.

DRV-16: Hz/Rpm Display

DRV►

Fault

 

 

12

 

nOn

 

12

None

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

None

nOn

 

 

 

 

 

 

 

 

 

Set this parameter to 0 [Hz] to display frequency, or to 1[Rpm] to display speed Ralated code

Related Functions: Changing the Hz/Rpm display affects the following parameter display.

DRV-00, 05, 06, 07, 14 FU1-20, 21,22, 24, 25, 32 FU2-32

I/O-03, 05, 08, 10, 20, 21, 22, 23, 24, 42, 43 EXT-08, 10

DRV-20: FU1 Group Selection (7-Segment keypad)

DRV-21: FU2 Group Selection (7-Segment keypad)

DRV-22: I/O Group Selection (7-Segment keypad)

DRV-23: EXT Group Selection (7-Segment keypad)

DRV-24: COM Group Selection (7-Segment keypad)

DRV-25: APP Group Selection (7-Segment keypad)

Select the desired group and press the PROG/ENT key to move into the desired group. The parameter in the group can be read and written after moving into the desired group.