Chapter 6 - Parameter Description [APP]

APP-26: Auto Change Mode Selection

APP►AutoCh_Mode

0

 

26

 

0

 

26

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

0

 

 

 

 

0

 

 

 

 

 

 

 

 

 

This function is used to change the running order of the motors to regulate their run-time when multiple motors are connected for MMC.

[0]: Not using Auto Change Function.

The inverter keeps the order Main motor RLY1 RLY2 RLY3 AUX and do not change the running order of auxiliary motors.

[1]: Auto Change Function is applied only to aux. motors. The inverter changes the order of auxiliary motors except the main motor connected to the drive. Running order is Main Motor RLY1 RLY2 RLY3 AUX. And then it is changed to Main Motor RLY2 RLY3 AUX RLY1.

[2]: Auto Change Function is applied to all motors. The inverter changes the order of all motors. The inverter operates the initial motor and the others are directly powered by commercial line. It should be used with Inter- lock function after configuring external inter-lock sequence circuit as shown below.

3 Phase

 

 

 

Input

 

 

 

R

S T

K1.1

K2.2

 

ACtion

 

 

 

U V W

 

 

K1

K2

M1M

[Wiring Diagram for Inter-Lock Configuration]

230VAC

 

 

 

SV-

 

 

RLY

CM

P1

P2

 

 

 

 

 

RLY

Auto

Main

 

Main

 

 

 

Auto

 

S1

 

 

S2

 

K2

K2

 

K1

K1

 

 

 

 

 

 

 

K1.1

K1

 

K2.1

K2

K1

K1.1

 

K2

K2.1

M1/ACti

M1/main

 

M2/ACti

 

 

 

 

onMast

 

[Sequence Circuit for Inter-Lock Configuration]

APP-27: Auto Change Time

APP-28: Auto Change Level

APP►AutoEx-intv

 

27

 

72:00

 

27

72:00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

72:00

 

 

72:00

 

 

 

 

 

 

 

 

 

 

 

APP►AutoEx-level

 

28

 

20

 

28

20 %

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

20 %

 

 

 

20

 

 

 

 

 

 

 

 

This function is used to protect motor from running alone for a long time by changing operation to other motor.

Auto Change is accomplished when the following conditions are satisfied:

1)The time set in APP-27 is over.

2)The actual value of controlling amount is less than the value set in APP-28.

3)Only one motor is running.

When above three conditions are met, the inverter stops the running motor, and changes motor to run by the order set in APP-26. and then continues operation according to new order.

If Auto Change Level (APP-28) is set to ‘0’, the function is initiated only when the motor is in Stop or Sleep state. The

6-67

Page 159
Image 159
HP 30 30 manual APP-26 Auto Change Mode Selection, APP-27 Auto Change Time APP-28 Auto Change Level, 7200, ACtion, M1M