HP 30 30 manual FU1-15 Hold Time, 1000, FU1-16 Pre-excitation Current, 00.0, 60.00

Models: 30 30

1 218
Download 218 pages 18.86 Kb
Page 97
Image 97

Chapter 6 - Parameter description [FU1]

FU1-15: Hold Time

FU1►

Hold Time

 

 

15

 

1000

 

15

1000 ms

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

1000 ms

 

 

1000

 

 

 

 

 

 

 

 

 

 

To set the time to maintain holding torque at zero speed and stop the operation in a shortest time during Vector_SPD mode operation

The inverter runs to maintain speed 0 for the hold time in Vector_SPD mode and decelerates to stop after the hold time elapse.

Output Speed [Hz or Rpm]

Output Voltage [V]

Hold time

Operation method during Hold Time:

FU1-7[Stop mode] Decel: speed zero control FU1-7[Stop mode] DC-brake

FU1-16: Pre-excitation Current

FU1► Flux Force

 

 

16

 

1 00.0

 

16

100.0 %

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

100.0 %

 

 

100.0

 

 

 

 

 

 

 

 

 

 

FU1-16 [Pre-excitation Current] is applied during FU1-14. When the motor magnetic flux increases to match the rated magnetic flux, pre-excitation current starts to decrease. When the motor magnetic flux reaches to the rated magnetic flux, the pre-excitation current matches the rated pre-excitation current.

Code

LCD display

Factory setting

Setting range

FU1-16

Flux Force

100 [%]

100 ~ 500 [%]

Motor magnetic flux

Excited current

FX-CM

Related Functions: FU2-34 [No Load Motor Current (RMS)] FU1-14 [Pre-excitation Time]

FU1-20: Maximum Frequency

FU1-21: Base Frequency

FU1-22: Starting Frequency

FU1►

Max freq

Hz

 

 

20

 

60.00

 

20

60.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

60.00 Hz

 

 

60.00

 

 

 

 

 

 

 

 

 

 

 

 

 

FU1►

Base freq

 

 

21

 

60.00

 

21

60.00

Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

60.00 Hz

 

 

60.00

 

 

 

 

 

 

 

 

 

 

 

FU1► Start freq

 

 

22

 

0.50

 

22

 

0.50

Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

0.50 Hz

 

 

0.50

 

 

 

 

 

 

 

 

 

 

 

FU1-20 [Maximum Frequency] is the maximum output frequency of the inverter. Make sure this maximum frequency does not exceed the rated speed of the motor. FU1-21 [Base Frequency] is the frequency where the inverter outputs its rated voltage. In case of using a 50Hz motor, set this to 50Hz.

FU1-22 [Starting Frequency] is the frequency where the inverter starts to output its voltage.

6-13

Page 97
Image 97