Chapter 4 – Function Settings

8) Operation-starting method

Parameter Name

Code

 

Description

 

 

 

 

FU2-20

Motor starting method:

 

[FU2-20]

: Power-on run,

Starting method

FU2-21

[FU2-21]

Restart after Fault Reset,

FU2-26

[FU2-26]

Number of Auto Restart Attempt

 

 

FU2-27

[FU2-27]

Delay Time Before Auto Restart

 

 

See parameter description for more.

 

FU2-22

Speed search function is available during Accel, trip,

 

FU2-23

Speed Search Selection

instant power failure, restart after fault reset and auto

FU2-24

 

restart. See parameter description for more.

 

FU2-25

 

 

 

4.1.3Advanced function 2 setting 1) PID operation

The inverter can be used to exercise process control, e.g. flow rate, air volume or pressure via PID feedback control.

 

Parameter Name

 

 

Code

 

 

Description

 

 

 

 

 

 

 

 

 

 

 

 

PID control setting

 

FU2-41~ FU2-60

 

Setting parameters for PID control

 

 

 

 

 

 

 

 

 

 

 

 

2) Jog and Multi-speed operation

 

 

 

 

 

 

Parameter Name

 

 

Code

 

 

Description

 

 

 

 

 

 

 

 

 

 

 

 

Multi function input

 

 

I/O-12 ~14

 

If I/O-12 ~14 are set to Speed-H, Speed-M, Speed-L,

 

terminal setting

 

 

EXT2 ~ 4

 

multi- speed operation up to speed 7 enable..

 

Filter time constant for

 

 

I/O-17

 

Effective for eliminating noise in the freq. setting circuit

 

input terminal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Speed reference value

 

 

DRV-05 ~ 7

 

Setting speed reference value for each step

 

 

I/O-21 ~ I/O-24

 

 

 

 

 

 

 

 

 

 

 

Accel/Decel time

 

 

I/O-25 ~ 38

 

Setting Accel/Decel time for each step

 

setting for each step

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Jog freq.

 

 

I/O-20

 

Setting jog freq for jog operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Speed-H

Speed-M

 

Speed-L

 

JOG

Speed Signal

 

Applied speed value

 

 

 

 

 

 

 

 

 

 

 

 

0

0

 

0

 

0

 

Speed 0

 

DRV-00

 

X

x

 

X

 

1

 

Jog freq.

 

I/O-20

 

0

0

 

1

 

0

 

Speed –1

 

DRV-05

 

0

1

 

0

 

0

 

Speed –2

 

DRV-06

 

0

1

 

1

 

0

 

Speed –3

 

DRV-07

 

1

0

 

0

 

0

 

Speed –4

 

I/O-21

 

1

0

 

1

 

0

 

Speed –5

 

I/O-22

 

1

1

 

0

 

0

 

Speed –6

 

I/O-23

 

1

1

 

1

 

0

 

Speed –7

 

I/O-24

4-7

Page 53
Image 53
HP 30 30 manual Advanced function 2 setting 1 PID operation, Jog and Multi-speed operation, Speed-H Speed-M Speed-L