Chapter 7 - Options

7.3.2Terminal Configuration

+24V DC

24V

Ground

Q1 EXTG NC

P4 P5 P6 CM NC GND V2 AM1 AM2 VR GND

7.3.3Terminal Description

 

Section

Terminal

Name

Description

 

 

P4, P5, P6

Multi-Function Input

Used as the extended function of P1, P2, P3

 

Contact Input

(I/O-12 ~ I/O-14).

 

 

 

 

 

CM

Common Terminal

Common terminal for P4, P5, P6

Input

 

VR

Power supply for V2

DC voltage output terminal for V2 (+12V, 10mA)

Analog

 

 

Analog voltage or current input terminal for frequency reference or

 

 

 

 

Frequency

V2

Analog Voltage Input

override. (0 ~ 10V DC, 4 ~ 20mA)

 

Reference

 

 

Connecting jumper pin (J1) select current input.

 

 

5G

Common Terminal

Common terminal for VR and V2

 

 

AM1

Analog Meter 1

Used to monitor one of Output Frequency, Output Current, Output

 

Analog Voltage

 

 

Voltage, DC link Voltage

Output

AM2

Analog Meter 2

(0 ~ 10V DC analog output, 1mA)

 

 

 

 

GND

Common Terminal

Common terminal for LM

 

Open Collector

Q1

Multi-function Output

Used as the extended function of AXA, AXC (I/O-44)

 

Output

EXTG

External Common Terminal

Common terminal for Q1

 

 

NC

Not Used

 

7.3.4Parameters of Sub-C Board

Code

Parameter Description

EXT-01

Sub Board Type Display

EXT-02

 

EXT-03

Multi-Function Input Terminal (P4, P4, P6) define

EXT-04

 

EXT-05

V2 Mode Selection

EXT-06

Filtering Time Constant for V2 Input Signal

EXT-07

Analog Voltage Input Signal (V2) Adjustment

EXT-08

 

Code

Parameter Description

EXT-09

Analog Voltage Input Signal (V2) Adjustment

EXT-10

 

EXT-30

Multi-function Output Terminal (Q1) define

EXT-40

 

EXT-41

AM1, AM2 Adjustment

EXT-43

 

EXT-43

 

 

 

7-11

Page 173
Image 173
HP 30 30 manual Q1 Extg NC P4 P5 P6 CM NC GND V2 AM1 AM2 VR GND, Parameters of Sub-C Board