Chapter 1 - Installation

1.6 Basic Wiring

DC Bus Choke (Optional)3

DC Bus Choke

Dynamic

Braking Unit

(Optional)

P N B1 B2

DB Unit(Optional)4 DB Resitor

DB Resistor

MCCB(OPTION)

P11 P21 N1

3 φ

R

 

 

230/460 V

S

 

 

50/60 Hz

T

 

 

 

G ( )

 

Forward Run/Stop

FX

 

 

Reverse Run/Stop

 

 

RX

 

 

Inverter Disable

 

 

BX

 

 

Fault Reset

 

 

RST

 

 

Jog

 

 

JOG

 

 

Multi-function Input 1

 

 

P1

 

 

Multi-function Input 2

Factory Setting:

 

P2

 

Multi-function Input 3

‘Speed-L’

 

P3

‘Speed-M’

 

 

‘Speed-H’

(N.O.) A

Common Terminal

 

CM

 

C

 

 

 

 

 

(N.C.) B

Potentiometer

Shield

 

 

(1 kohm, 1/2W)

 

Power supply for

AXA

 

VR speed signal:

AXB

 

 

+ 11V, 10mA

 

V1

Speed signal input:

 

 

 

0 ~ 10V

 

I

Speed signal input:

 

4 ~20mA (250ohm)

5G

Common for

Speed signal Input2

VR, V1, I

 

U

VMOTOR

W

FM

+

FM Output Frequency Meter

 

(0~10V Linear)

5G

Fault output relay lless than AC250V, 1A lless than DC30V, 1A

Multi-function output relay1 lless than AC250V, 1A lless than DC30V, 1A Factory setting: ‘Run’

Note)

Main Circuit Terminals

Control Circuit Terminals.

1.The terminal configuration varies depend on the model number. Please refer to the ‘1.7 Power terminals’.

2.Analog speed command may be set by Voltage, Current or both.

3.When installing the DC Reactor, the Common Busbar between P1 and P2 must be removed.

4.1 ~ 10 HP inverters have on-board braking circuit. Braking resistors are only included for 1 ~ 5 inverters. 15 ~ 30 HP inverters need optional braking unit and resistor for dynamic braking.

1-7