Chapter 6 - Parameter Description [APP]

APP►Start freq3

 

 

 

13

 

49.99

 

13

49.99

Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

49.99

Hz

49.99

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

APP►Start freq4

 

 

 

14

 

49.99

 

14

49.99

Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

49.99

Hz

49.99

 

 

 

 

 

 

 

 

 

 

 

The inverter turns on AUX, RLY1, RLY2, and RLY3 in order if the output frequency is over the frequencies set in APP-11 to APP-14, respectively, and the time is over APP- 19.

APP-15: Stop Frequency of Aux. Motor 1

APP-16: Stop Frequency of Aux. Motor 2

APP-19: Delay Time before Operating Aux. Motor

APP-20: Delay Time before Stopping Aux. Motor

APP►Aux Start DT

 

 

19

 

60.0

 

19

60.0 sec

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

60.0 sec

 

 

60.0

 

 

 

 

 

 

 

 

 

 

Sets the time the inverter waits before starting the auxiliary motors.

APP►Aux Stop DT

 

 

20

 

60.0

 

20

60.0 sec

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

60.0 sec

 

 

60.0

 

 

 

 

 

 

 

 

 

 

Sets the time the inverter waits before stopping the auxiliary motors.

APP-17: Stop Frequency of Aux. Motor 3

APP-18: Stop Frequency of Aux. Motor 4

APP►Stop freq1

 

 

 

15

 

15.00

 

15

15.00 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

15.00

Hz

15.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

APP►Stop freq2

 

 

 

16

 

15.00

 

16

15.00 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

15.00

Hz

15.00

 

Output

Frequency

Start freq 1 (APP-11)

Stop freq 1(APP-15)

Starting

Freq.

Aux start DT(APP-19)

Frequency rise according to

APP-19

Frequency drop according to

APP-20

Aux stop DT(APP-20)

Flow

Aux. Motor

Start

When the Flo increse

Start/Stop

Stop

When the Flo decrese

APP►Stop freq3

 

 

17

 

15.00

 

17

15.00 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

15.00

Hz

15.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

APP►Stop freq4

 

 

 

18

 

15.00

 

18

15.00 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

15.00

Hz

15.00

 

 

 

 

 

 

 

 

 

 

The inverter turns off RLY3, RLY2, RLY1, and AUX in order if the output frequency is below the frequencies set in APP-15 to APP-18, respectively, and the time is over APP-20.

[Aux. Motor Start/Stop with MMC]

APP-21: The Number of Aux. Motors

APP►Nbr Aux’s

 

4

 

21

 

4

 

21

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

4

 

 

 

 

4

 

 

 

 

 

 

 

 

 

Sets the number of auxiliary motors connected to the inverter.

6-65

Page 157
Image 157
HP 30 30 manual 49.99, 60.0, APP-21 The Number of Aux. Motors