HP 30 30 manual SL P-gain, SL I-gain, PID Ref, PID Out Dir, PID P-gain, PID I-time, PID D-time

Models: 30 30

1 218
Download 218 pages 18.86 Kb
Page 68
Image 68

Chapter 5 - Parameter List

Code

Description

Keypad Display

Setting Range

 

Units

Factory

Adj.

Page

LCD

 

7-Segment

LCD

 

7-Segment

Default

During

 

 

 

 

 

Run

 

FU2-43

Stator Inductance of

Ls

43

0 to (depending on FU2-30) [mH]

 

 

No

 

Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FU2-44

Rotor Time Constant

Tr

44

0 to (depending on FU2-30) [mH]

 

 

No

 

FU2-45

P Gain for Sensorless

SL P-gain

45

0 to 32767

 

1

1000

Yes

 

Control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6-2

FU2-46

I Gain for Sensorless

SL I-gain

46

0 to 32767

 

1

100

Yes

 

 

Control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FU2-47

PID Operation Selection

proc PI mode

47

No

 

 

0

-

No

No

6-2

Yes

 

 

1

 

 

 

 

 

 

 

 

 

 

 

FU2-4822

PID Reference

PID Ref

 

 

Ramp freq.

 

 

0

-

Ramp freq.

No

6-2

 

Frequency Selection

 

48

Target freq.

 

 

1

 

 

 

 

 

 

 

 

 

Freq mode

 

 

0

 

 

 

 

 

 

 

 

 

Keypad-1

 

 

1

 

 

 

 

 

PID Reference Mode

PID Ref Mode

 

 

Keypad-2

 

 

2

-

Freq mode

No

6-2

FU2-49

Selection

49

V1

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

I

 

 

4

 

 

 

 

 

 

 

 

 

V2

 

 

5

 

 

 

 

FU2-50

PID Output Direction

PID Out Dir

50

Ramp freq.

 

 

0

-

Ramp freq.

No

6-2

Selection

Target freq.

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PID Feedback Signal

 

 

 

I

 

 

0

 

 

 

 

FU2-51

PID F/B

51

V1

 

 

1

-

I

No

 

Selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V2

 

 

2

 

 

 

 

FU2-52

P Gain for PID Control

PID P-gain

52

0 to 999.9 [%]

 

0.1

100.0 [%]

Yes

 

FU2-53

I Gain for PID Control

PID I-time

53

0 to 32.0 [sec]

 

0.1

30.0 [sec]

Yes

6-2

FU2-54

D Gain for PID Control

PID D-time

54

0 to 999.9 [msec]

 

0.1

0.0 [msec]

Yes

 

 

FU2-55

High Limit Frequency for

PID +limit

55

0 to 99.99 [Hz]

 

0.01

60.00 [Hz]

Yes

 

PID Control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FU2-56

Low Limit Frequency for

PID -limit

56

0 to 99.99 [Hz]

 

0.01

60.00 [Hz]

Yes

 

PID Control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FU2-57

PID Output Inversion

PID Out Inv.

57

No

 

 

0

-

No

No

 

Yes

 

 

1

 

 

 

 

 

 

 

 

 

6-2

FU2-58

PID Output Scale

PID OutScale

58

0 to 999.9 [%]

 

0.1

100 [%]

No

FU2-59

PID P2 Gain

PID P2-gain

59

0 to 100 [%]

 

0.1

100 [%]

No

 

FU2-60

P Gain Scale

P-gain Scale

60

0 to 100 [%]

 

0.1

100 [%]

No

 

FU2-69

Accel/Decel Change

Acc/Dec ch F

69

0 to FU1-20

 

 

 

No

6-2

Frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FU2-70

Reference Frequency for

Acc/Dec freq

70

Max freq

 

 

0

-

Max freq

No

6-2

Accel and Decel

Delta freq

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.01 [sec]

 

 

0

 

 

 

 

FU2-71

Accel/Decel Time Scale

Time scale

71

0.1 [sec]

 

 

1

0.01

0.1 [sec]

Yes

6-2

 

 

 

 

 

1 [sec]

 

 

2

 

 

 

 

22Code FU2-48 through FU2-60 appears only when FU2-47 is set to ‘Yes’.

5-8

Page 68
Image 68
HP 30 30 manual SL P-gain, SL I-gain, PID Ref, PID Out Dir, PID P-gain, PID I-time, PID D-time, PID +limit, PID -limit