Chapter 2 - Operation

2.3.17-Segment Keypad Display

1)Parameter Group

DRV FU1 FU2 I / O EXT

2) Parameter Code and

3) Output Frequency during run,

Operating Status

Command Frequency during stop

 

Display

Description

1) Parameter Group

Displays the parameter groups of DRV, FU1, FU2, I/O, EXT, COM, APP groups.

 

Each LED is lit when its parameter group is selected and blinks when the parameter code is located on

 

DRV 20, DRV 21, DRV 22, DRV 23, DRV 24, and DRV 25.

2) Parameter Code and

Displays the code of a group. Rotate the encoder knob to move through 0 ~ 99 codes.

Operating Status

Displays the operation information.

 

[First digit]

 

F: Forward operation

 

r: Reverse operation

 

[Second digit]

 

d: DC Braking

 

J: Jog Terminal Input

 

1~8: Step Frequency Input (Displays the Step of the Auto operation)

 

[Two digits] - when the reference is lost.

 

LP: Loss of Reference from the Option Board (DPRAM fault)

 

Lr: Loss of Reference from the Option Board (Communication network fault)

 

Lv: Loss of Analog Frequency Reference (V1: 0~10V)

 

LI: Loss of Analog Frequency Reference (I: 4~20mA)

 

LX: Loss of Reference from the Sub-Board

3) Output Frequency,

Displays the Output Frequency during run.

Command Frequency

Displays the Command Frequency during stop.