Chapter 8 - Troubleshooting & Maintenance

8.2 Fault Remedy

Protective

 

Cause

 

Remedy

Function

 

 

 

 

 

 

 

1)

Acceleration/Deceleration time is too short compared to

1) Increase Accel/Decel time

 

 

the GD²of the load

2) Increase inverter capacity.

 

2)

Load is larger than the inverter rating

3) Operate after motor has stopped

Over Current

3)

Inverter turns output on when the motor is free running.

4) Check output wiring

4)

Output short or ground fault has occurred

5) Check mechanical brake operation

Protection

5)

Mechanical brake of the motor is operating too fast

6) Check cooling fan

 

 

6)

Components of the main circuit have overheated due

(Caution) Operating inverter prior to correcting fault

 

 

to a faulty cooling fan

may damage the IGBT

 

 

 

 

Ground Current

1) Ground fault has occurred at the output wiring of inverter.

1)

Investigate the output wiring of inverter

Protection

2) The insulation of the motor is damaged due to heat.

2)

Exchange motor

 

1)

Acceleration time is too short compared to the GD²of

1)

Increase deceleration time

Over Voltage

 

load

2)

Use regenerative resistor option

Protection

2) Regenerative load at the output

3)

Check line voltage

 

3)

Line voltage high

 

 

Current Limit

1) Load is larger than the inverter rating

1)

Increase capacity of motor and inverter

Protection

2) Selected incorrect inverter capacity

2)

Select correct inverter capacity

(Overload

3) Set incorrect V/F pattern

3)

Select correct V/F pattern

Protection)

 

 

 

 

 

1)

Damage due to repeated over current protection

Exchange the fuse

Fuse Damage

2) Damage due to instant deceleration when motor is at an

(Caution) The IGBT receives damages on many

 

 

excessive excitation status.

occasions when Fuse Open Trip occurs

 

1)

Cooling fan damaged or an alien substance inserted

1)

Exchange cooling fans and/or eliminate alien

Heat Sink

2) Cooling system has faults

 

substance

Overheat

3) Ambient temperature high

2)

Check for alien substances in the heat sink

 

 

 

3)

Keep ambient temperature under 40

 

1)

Motor has overheated

1)

Reduce load and/or running duty

 

2)

Load is larger than inverter rating

2)

Increase inverter capacity

Electronic

3)

ETH level too low

3)

Adjust ETH level to an appropriate level

4)

Selected incorrect inverter capacity

4)

Select correct inverter capacity

Thermal

5)

Set incorrect V/F pattern

5)

Select correct V/F pattern

 

 

6)

Operated too long at low speeds

6)

Install a cooling fan with a separate power supply

 

 

 

 

Ext Trip-A

External fault has occurred

Eliminate fault at circuit connected to external fault

terminal or cause of external fault input

 

 

 

Ext Trip-B

External fault has occurred

Eliminate fault at circuit connected to external fault

terminal or cause of external fault input

 

 

 

 

1)

Line voltage low

1)

Check line voltage

Low Voltage

2)

Load larger than line capacity is connected to line

2)

Increase line capacity

 

(welding machine, motor with high starting current

3)

Exchange magnetic switch

Protection

 

 

connected to the commercial line)

 

 

 

 

 

 

 

3)

Faulty magnetic switch at the input side of the inverter

 

 

 

1)

Short has occurred between the upper and lower IGBT.

1)

Check IGBT

Over Current 2

2)

Short has occurred at the output of the inverter

2)

Check output wiring of inverter

3) Acceleration/Deceleration time is too short compared to

3)

Increase acceleration time

 

 

the GD²of load

 

 

Output Phase

1) Faulty contact of magnetic switch at output

1)

Check magnetic switch at output of inverter

Open

2) Faulty output wiring

2)

Check output wiring

Over Speed

1) Faulty wiring of Encoder (A, B)

1) Check Encoder A, B signal wiring and wire them

8-3

Page 197
Image 197
HP 30 30 manual Fault Remedy, Protective Cause Remedy