-114-
19. HARDWARE CHECK 19.5 Alarm Output Check
This check is only available for the alarm output (option). It checks the relay drive circuits and relays by outputting
the shorted (on) or open (off) signals at the specified alarm output terminals (relay Nos.).

Check Flow Chart

Operation screen
[Engineering mode selection]
( + )
3 sec. or more




[Selecting check]




[Displaying check 1]





[Displaying check 2]




[Selecting alarm output]




[Displaying replay No.]


[Programming relay No.]


[Selecting output]




Confirming output
* N.C terminals are provided for the
mechanical relay “c” contact output.
Output Output
condition N.O - COM
Off 10M or
more
MOS relay On 50 or less
Off 10M or
more
Mechanical relay
(Common for “a”
and “c” contacts) On 0.1 ore less
Press or to switch
Check 1 and 2.
(1)

: Alarm output check
(2)

: Remote contacts input check
(3)

: Communications interface check
The programming range of relay Nos.
are 1 to 6 for AL and 01 to 12 for AH.
The selection of output (on or off) is
effective at the moment is
pressed. The previous output status is
kept until then.
Cursor Check
Cursor
(1) (3)(2)
Cursor
Cursor
Rela
y
No.
Open Short circuiting
Resistance values between terminals
Relay No. for alarm output terminals
DISP
°
C
°F
ENTRY
%
/
°
C
°F
ENTRY
0
CLEAR
6
A - Z
ENTRY
ENTRY
%
/
Cursor
Cursor
Cursor
Ref. 1
Ref. 2
Ref. 3
Ref. 4
Types of check 2
Reference 2
Check 1 and 2 switching
Reference 1
Programming relay No.
Reference 3
Output
Reference 4
2 sec. or more
SHIFT
6
A – Z