Omega RS-422A, RS-485 Connections, Example of 9-in connector, RD200/RD2800 hybrid recorders

Models: RD2800 RD200

1 134
Download 134 pages 14.81 Kb
Page 24
Image 24

4.CONNECTIONS

4.7 Communications terminals

3RS-422A, RS-485 Connections

RS-422/485 communications interface is connected to a personal computer via a line converter (our Model SC8-10: sold separately). Three signals of SD, RD and SG are used between the line converter and the personal computer but any control signal is not used. Wiring processing for control signal in a connector is

necessary in the same as

2

 

RS-232C connections.

1) RS-422A

 

Personal computer

Line converter

(9-pin or 25-pin connector)*

(SC8-10)

RD 2

SD 3

ER 4

SG 5

DR 6

RS 7

CS 8

Example of 9-in connector

1 RD

2 SD

3 SG

4

RDA 5

RDB 6

SDA 7

SDB 8

RD200/RD2800 hybrid recorders

 

(1)

(2)

(3)

 

SDA

SDA

SDA

 

SDB

SDB

SDB

 

RDA

RDA

RDA

 

RDB

RDB

RDB

Termination

SG

SG

SG

resistance

 

 

 

100 Ω, 1/4W

Within 15 m

 

Within a total length of 1.2 km (max. 31 recorders)

 

 

 

 

*For the details of the wiring, refer to 2 RS-232C connections.

2) RS-485

Personal computer

(9-pin or 25-pin connector)*

RD 2

SD 3

ER 4

SG 5

DR 6

RS 7

CS 8

Example of 9-in connector

Line converter

(SC8-10)

1 RD

2 SD

3 SG

4

RDA 5

RDB 6

SDA 7

SDB 8

RD200/RD2800 hybrid recorders

(1)

(2)

(3)

SA

SA

SA

SB

SB

SB

SG

SG

SG

Termination

resistance

100 Ω, 1/4W

Within 15 m Within a total length of 1.2 km (max. 31 recorders)

*For the details of the wiring, refer to 2 RS-232C connections”.