22. SPECIFICATIONS

10 Option

1) Alarm outputs

Output types: cAlarm point output d FAIL output e Chart paper end (C.End) output

Numbers of outputs: RD200 … 6 points RD2800 …6 or 12 points

Contact capacity (with resistive load):

cMOS relay output … 240 V (AC, DC), 50 mA (AC, DC)

dMechanical relay (Common for “a” and “c” contacts) …

100VAC 0.5 A, 240VAC 0. 2A, 100VDC 0.3 A Output wiring: AND/OR output selection is available for each

alarm points (including FAIL and C.End) Relay coil phase: Energize/Not energize selectable* Relay output latch: Hold/Not hold selectable* Alarm display latch: Hold/Not hold selectable*

*Common to all relays

Dimension: The following length will be added for the depth. RD200…14 mm (MOS relay, Mechanical “c”

contact)

25 mm (Mechanical “a” contact) RD2800…16 mm (MOS relay, Mechanical “c”

contact)

27 mm (Mechanical “a” contact)

2) Remote contacts

Input terminals: 4 points (Common terminals: 2 points)

Input signal: Contact (Open/Shorted)

Voltage when the contact is open: Approx. 5 V

Current when the contact is shorted: Approx. 2 mA

Operations: Up to 4 input terminals can be selectable in the following table.

 

Operation

Terminal

c Printing ON/OFF, 3 chart speeds

2

d Message (No.1 to No.5) printing

4

e Message (No. 1 and No. 2) printing

2

f Digital data printing

1

g List 1 printing

1

h List 2 printing

1

i List 3 printing

1

j Operation record A

1

k Operation record B

1

• Operation record C

1

11

Operation record D

1

12

Reset of totalization*

1

*This operation is only available for the “totalization” (option).

3) Printing format

Trace printing format, c Automatic range shift, d Compressed/Expanded or e Zone scale, is selectable for each channel.. The format e is common to all channels.

Automatic

Printing area can be divided up to 5 ranges. It

switches the range according to the measured

range-shift

values automatically for printing.

 

Compressed/

Specific printing range is compressed or

Expanded

expanded for printing.

 

Printing area is divided into 2 to 4 zones*. Data

Zone scale

of each channel is printed in the relevant zone.

 

*RD200 … 2, RD2800 … 2 to 4

4) Others

Options

 

Detail

 

Communications

Specify one of the following modes.

interface*

RS-232C, RS-422A, RS-485

 

Capable up to ±50mA DC by connecting an

Input resistance

input resistance to

the

measuring input

terminal.

 

 

 

for current input*

 

 

 

100: Applicable current

±50mA

 

 

250: Applicable current

±20mA

 

One of following math expressions is

 

selectable for each channel.

 

Addition,

subtraction, multiplication, division,

Math

natural

logarithm,

logarithm, exponential,

square root, temperature/humidity, maximum,

expression*

minimum, average value, absolute value,

 

data communications input*, flow rate

 

compensation.

 

 

 

*This function is only available for the

 

“communications interface” (option).

 

Totalizing measured values and calculation

 

results. Reset function is executed with

Totalizing*

programmed intervals or

remote contacts

signals*.

 

 

 

 

 

 

 

 

*This function is only available for the

 

“remote contacts” (option).

 

Transmitter

Power supply unit for the transmitter

power supply*

generating input signal to the recorder

16 m chart paper

RD200 only …. Total chart paper length of

 

15.6 m

 

 

 

* Exclusive instruction manual is provided.

-130-