22. SPECIFICATIONS
10
Option
1) Alarm outputs
Output types: cAlarm point output d FAIL output e Chart paper end (C.End) output
Numbers of outputs: RD200 … 6 points RD2800 …6 or 12 points
Contact capacity (with resistive load):
cMOS relay output … 240 V (AC, DC), 50 mA (AC, DC)
dMechanical relay (Common for “a” and “c” contacts) …
100VAC 0.5 A, 240VAC 0. 2A, 100VDC 0.3 A Output wiring: AND/OR output selection is available for each
alarm points (including FAIL and C.End) Relay coil phase: Energize/Not energize selectable* Relay output latch: Hold/Not hold selectable* Alarm display latch: Hold/Not hold selectable*
*Common to all relays
Dimension: The following length will be added for the depth. RD200…14 mm (MOS relay, Mechanical “c”
contact)
25 mm (Mechanical “a” contact) RD2800…16 mm (MOS relay, Mechanical “c”
contact)
27 mm (Mechanical “a” contact)
2) Remote contacts
Input terminals: 4 points (Common terminals: 2 points)
Input signal: Contact (Open/Shorted)
Voltage when the contact is open: Approx. 5 V
Current when the contact is shorted: Approx. 2 mA
Operations: Up to 4 input terminals can be selectable in the following table.
| Operation | Terminal |
c Printing ON/OFF, 3 chart speeds | 2 | |
d Message (No.1 to No.5) printing | 4 | |
e Message (No. 1 and No. 2) printing | 2 | |
f Digital data printing | 1 | |
g List 1 printing | 1 | |
h List 2 printing | 1 | |
i List 3 printing | 1 | |
j Operation record A | 1 | |
k Operation record B | 1 | |
• Operation record C | 1 | |
11 | Operation record D | 1 |
12 | Reset of totalization* | 1 |
*This operation is only available for the “totalization” (option).
3) Printing format
Trace printing format, c Automatic range shift, d Compressed/Expanded or e Zone scale, is selectable for each channel.. The format e is common to all channels.
Automatic | Printing area can be divided up to 5 ranges. It | |
switches the range according to the measured | ||
values automatically for printing. | ||
| ||
Compressed/ | Specific printing range is compressed or | |
Expanded | expanded for printing. | |
| Printing area is divided into 2 to 4 zones*. Data | |
Zone scale | of each channel is printed in the relevant zone. | |
| *RD200 … 2, RD2800 … 2 to 4 |
4) Others
Options |
| Detail |
| ||
Communications | Specify one of the following modes. | ||||
interface* | |||||
| Capable up to ±50mA DC by connecting an | ||||
Input resistance | input resistance to | the | measuring input | ||
terminal. |
|
|
| ||
for current input* |
|
|
| ||
100Ω: Applicable current | ±50mA | ||||
| |||||
| 250Ω: Applicable current | ±20mA | |||
| One of following math expressions is | ||||
| selectable for each channel. | ||||
| Addition, | subtraction, multiplication, division, | |||
Math | natural | logarithm, | logarithm, exponential, | ||
square root, temperature/humidity, maximum, | |||||
expression* | minimum, average value, absolute value, | ||||
| data communications input*, flow rate | ||||
| compensation. |
|
| ||
| *This function is only available for the | ||||
| “communications interface” (option). | ||||
| Totalizing measured values and calculation | ||||
| results. Reset function is executed with | ||||
Totalizing* | programmed intervals or | remote contacts | |||
signals*. |
|
|
| ||
|
|
|
| ||
| *This function is only available for the | ||||
| “remote contacts” (option). |
| |||
Transmitter | Power supply unit for the transmitter | ||||
power supply* | generating input signal to the recorder | ||||
16 m chart paper | RD200 only …. Total chart paper length of | ||||
| 15.6 m |
|
|
|
* Exclusive instruction manual is provided.
-130-