11. OTHER PROGRAMMING
11.6 Alarm Deadband
A deadband can be programmed between
Press | SHIFT and ° | simultaneously in the operation screen for 3 seconds or more to display the [Alarm |
| C |
|
deadband] programming screen. This programming is common to all alarm points.
1 Alarm Deadband
●An alarm activates when a measured value exceeds the alarm value. The alarm reset is executed at a value that is lower than the alarm value. This difference is called the deadband and is specified with a scale width
(%).
●The programming range is 0.1 to 9.9% and can be programmed in 0.1% increments. The default is 0.1%.
2 Programming Flow Chart
<Example> From 0.1% to 0.5%
|
|
|
|
|
| Alarm deadband |
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Low alarm |
|
|
|
|
|
| High alarm |
|
|
| ||||
|
|
|
| Dead |
|
|
|
|
|
|
| Dead |
|
|
| ||
| ON |
| band |
|
|
|
|
|
|
| band | ON | |||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(Activation) |
|
|
| OFF | OFF |
|
|
|
| (Activation) | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| (Reset) | (Reset) |
|
|
|
|
|
| ||||
MIN Alarm value |
| MAX | MIN | Alarm value MAX |
Operation screen
[Check]
DISP
3 sec. or
( SHIFT + °C )more
Decimal point is fixed.
|
| SET |
|
|
|
[To be ready for programming] | END |
|
|
| |
|
|
|
| ||
|
|
|
|
| |
| | ||||
|
|
|
|
|
|
|
|
|
| Cursor | |
|
| °F | 5 |
| |
[Programming deadband] | , DATAI | ||||
|
|
|
| ||
|
|
|
|
| |
| | ||||
|
|
|
|
|
|
|
|
|
|
|
|
Deadband
ENTRY
Stored
-67-