Diagnostics data
6.1 Diagnostics by means of LED displays
LED displays
The following table provides an overview of all relevant LED display combinations. Each LED can be lit in yellow, red, or green color. The color which corresponds with the LED signal state is also defined.
Table | Diagnostics by means of LED display |
|
|
|
| |
|
|
|
|
|
| |
Meaning |
| RDY | RUN/STOP | OUT > 5V | SF/BF: | |
SINAMICS Integrated ready for operation | 1 | x | x | x | ||
|
|
| (green) |
|
|
|
SINAMICS Integrated in fault state | Λ | x | x | x | ||
|
|
| (red) |
|
|
|
Startup of the D410 without CF card or with CF card without valid | 0,5/1 | 1 | 0 | 0 | ||
operating system (the bootloader may be defective) | (red) | (red) |
|
| ||
Write access to CompactFlash Card | 2/1 | x | x | x | ||
|
|
| (green) |
|
|
|
SIMOTION ready for operation | x | 1 | x | x | ||
|
|
|
| (green or |
|
|
|
|
|
| yellow) |
|
|
Fault event to which the user program (SIMOTION) cannot | Λ | Λ | x | Λ | ||
respond, or firmware error at the PROFINET interface. | (red) | (red) |
| (red) | ||
The following actions may be required to rectify the fault: |
|
|
|
| ||
• | Power OFF/ON |
|
|
|
| |
• Check of the CompactFlash Card |
|
|
|
| ||
• |
|
|
|
| ||
• Replacement of SIMOTION D410 |
|
|
|
| ||
A warning is present on the SINAMICS Integrated. | 1 | x | x | x | ||
This state can occur, for example, when the | (yellow) |
|
|
| ||
components are loaded but have not been inserted. |
|
|
|
| ||
|
|
|
|
| ||
Ethernet LED (only for SIMOTION D410 PN) | x | x | x | 2/1 | ||
DCP flashing of the module activated in the HW Config at Target |
|
|
| (green) | ||
system > Ethernet > Edit Ethernet node > "Search" button > |
|
|
|
| ||
"Flashing" button |
|
|
|
| ||
Priority: 0 1) |
|
|
|
|
| |
Active interrupt which can be acknowledged (alarm, message, | x | x | x | 1 | ||
note) |
|
|
|
| (red) | |
Priority: 1 1) |
|
|
|
|
| |
Bus fault |
| x | x | x | 2/1 | |
• PROFIBUS master: At least one slave is missing |
|
|
| (red) | ||
• PROFIBUS slave: No parameter assignment master found |
|
|
|
| ||
• PROFINET: Failure of a connected I/O device; at least one of |
|
|
|
| ||
| the assigned I/O devices cannot be addressed; faulty or |
|
|
|
| |
| missing configuration data. |
|
|
|
| |
Priority: 2 1) |
|
|
|
|
| |
Sublicensing of technology/option objects | x | x | x | 0.5/1 | ||
Priority: 3 1) |
|
|
|
| (red) | |
Upgrade/downgrade operation running. | 0,5/1 | x | x | x | ||
|
|
| (yellow) |
|
|
|
136 | D410 |
Commissioning Manual, 08/2008 Edition |