Configuring SIMOTION D410

3.4 Configuring PROFINET (only for D410 PN)

Initializing SIMOTION D410

SIMOTION D410 must be assigned an IP address and a device name in order to enable downloading of the project. This is performed online on the SIMOTION device using the so- called "node initialization". To perform the node initialization, the programming device / PC must be connected with the SIMOTION D410 PN. SIMOTION SCOUT must be open.

1.Click the "Reachable nodes" button on the SIMOTION SCOUT toolbar. The newly opened "Reachable nodes" window shows the SIMOTION D410 device as "bus node" with the address 0.0.0.0 and a name.

2.Select the "Bus node" entry and open the "Edit Ethernet node..." function in the context menu. The "Edit Ethernet Node" dialog box opens.

3.Enter a name in the "Device name" field.

4.Click the "Assign name" button and confirm the displayed message with "OK."

5.Enter an appropriate IP address for the Ethernet subnet in the "IP address" field.

6.Enter an appropriate subnet mask for the Ethernet subnet in the "Subnet mask" field.

7.If required, enter the data for a network gateway.

8.Click "Assign IP Configuration". The entered data is assigned to the SIMOTION device.

9.Confirm the displayed message with "OK".

10.Click the "Close" button to close the "Edit Ethernet Node" window.

11.Click the "Update" button in the "Reachable Nodes" window. The SIMOTION D410 device is now displayed as "Geraet_01" with the type designation of the device and the assigned IP address.

12.Click the "Close" button to close the "Reachable Nodes" window.

54

D410

Commissioning Manual, 08/2008 Edition

Page 54
Image 54
Siemens appendix Initializing Simotion D410