Commissioning (software)
4.2 Configuring the system in offline mode
D410
70 Commissioning Manual, 08/2008 Edition
4.2.4 Aligning HW Config
After having completed the configuration of all SINAMICS components, align the data with
HW Config.
Proceed as follows:
1. Open the "Configuration" entry in the "SINAMICS_Integrated" tree in the Project
Navigator. The "SINAMICS_Integrated - Configuration" dialog box opens with a list of
configured drive objects.
The question marks in the I/O address fields indicate that you have not yet defined the
I/O addresses of the drive objects.
Figure 4-10 Configuration prior to HW Config alignment
Note
Drive objects without address must be positioned at the end of the list, for otherwise it is
not possible to align HW Config ("Align with HW Config"). To move the order of a drive
object without address, select the associated drive object and move it downwards using
the arrow key.
2. Click "Align with HW Config" in order to assign addresses to the configured components.
The addresses are written to HW Config.