Commissioning (software)
4.6 Using
4.6.4Configuring free message frames by means of BICO
Overview
For the "free message frame configuring using BICO", dedicated message frames for the data transmission are assigned to the associated drive objects (e.g. terminal modules). Message frame type: Free message frame configuring using BICO (only slaves)
To allow SIMOTION to access the SINAMICS drive signals, e.g. I/Os, they must be interconnected to the SINAMICS using BICO to the message frame. The "free message frame configuring using" is a preferred solution when I/Os are to be divided
Table | Drive object: Maximum number of PSDs |
| |
|
|
|
|
Drive object |
| Maximum number of PSDs for the configuring of the PROFIBUS | |
|
| message frames |
|
|
| Input data | Output data |
|
| (from the SIMOTION D | (from the SIMOTION D |
|
| viewpoint) | viewpoint) |
TM15 DI/DO |
| 5 | 5 |
TM31 |
| 5 | 5 |
TM41 |
| 19 | 16 |
Control Unit (CU) | 15 | 5 |
Free message frame configuring using the TM31 as example
The example describes the interconnection of a signal to the TM31 connected to a
SIMOTION D410.
Steps in configuring
●Configure a
●Interconnect the message frame for TM31
●Create I/O variables in SIMOTION SCOUT
Prerequisite
You have already created a project and configured a drive.