Commissioning (software)

4.3 Configuring the system in online mode

Procedure

Now go ahead and adapt your components to suit the application.

Run the wizards for all DRIVE-CLiQ components to be customized and configure the motor, encoder, and process data message frames (PROFIBUS message frame type).

This procedure corresponds with the description in chapter "Configuring the system in offline mode".

Note

If only the message frame type needs to be selected for the edit, you can also set this in the "Configuration" screen form of the drive element. A HW Config match is then required.

Configuring the system in offline mode (Page 62)

4.3.5Aligning HW Config

See also

Aligning HW Config (Page 70)

4.3.6Download the project to SIMOTION D410

After having aligned HW Config, download the configuration to SINAMICS Integrated.

1.Save and compile the project.

2.Go online to SIMOTION D410.

3.Select the "Download project to target system" command to download the project to SIMOTION D410. The connection to SINAMICS Integrated is activated automatically.

Drive programming and commissioning is completed. You can now test the drive using the drive control panel.