Commissioning (software)

4.9Testing the configured drive using the drive control panel

4.9Testing the configured drive using the drive control panel

You can test a configured drive using the drive control panel where you can define a speed value by setting a scaling factor. The drive control panel should only be used for commissioning.

Prerequisites

The project has been downloaded to the target system.

SIMOTION SCOUT is in online mode.

The drive is not in use by a current project in RUN mode.

WARNING

Make sure that the drive test does not pose any risk to persons.

Testing the drive using the drive control panel

1.Change to the configured drive in the Project Navigator and open the drive control panel by selecting "Commissioning" > "Control panel". The drive control panel opens in the detail view.

Figure 4-28 Drive control panel

2.In order to view the control range and axis diagnostics data, click "Show/hide control" and Show/hide axis diagnostics".

3.Click "Assume control priority". The "Assume Control Priority" dialog box opens.