Siemens appendix Rules for Simotion D410 PN

Models: D410

1 150
Download 150 pages 59.82 Kb
Page 59
Image 59

Configuring SIMOTION D410 3.4 Configuring PROFINET (only for D410 PN)

Rules for SIMOTION D410 PN

The general rule for SIMOTION D410 specifies that the send cycle (D410 PN) forms the basic clock of the cycle system. All cycles longer than this basic clock must be an integer multiple of the basic clock.

This rule also applies to SINAMICS cycles, if one of the successive cycles is longer than the basic clock:

Speed controller p115[1]

Flow controller p115[2]

Setpoint channel p115[3]

Position controller p115[4]

Positioning p115[5]

Technology controller (p0115[6])

Onboard I/O p0799

Terminal module I/O p4099

The corresponding cycle must be an integer multiple of the basic clock.

If any change to the send cycle violates this rule you must also change the SINAMICS cycles. In order to change the cycles in the Expert list of SIMOTION SCOUT, select the "Control_Unit" from "SINAMICS_Integrated" in the Project Navigator, and then open the "Expert List" by selecting the "Expert" command from the shortcut menu.

Example: A default value of 4 ms is set at the SINAMICS setpoint channel. If setting a DP cycle of 3 ms you must set an integer multiple value as required at the setpoint channel, for example, 3 ms or 6 ms.

Note

An overview of errors reported in SINAMICS Integrated is provided in the SINAMICS S Parameter Manual

D410

59

Commissioning Manual, 08/2008 Edition

Page 59
Image 59
Siemens appendix Rules for Simotion D410 PN