Commissioning (software) 4.12 Deleting data

How to reset the memory:

1. Set the MRES mode on the DIL switch (see the picture below).

21

      

6FKDOWHUVWHOOXQJ 21  

6FKDOWHUVWHOOXQJ 2))  

Figure 4-33 Switch position MRES

The STOP LED begins to flash.

2.Set DIL switch 1 to ON (STOP mode) after the STOP LED is lit in yellow color.

3.Return the DIL switch to MRES mode within three seconds. The memory is now being reset.

4.Wait for SIMOTION D410 to complete its restart. Set DIL switch 1, 2 and 3 to ON (RUN mode).

The STOP LED lights after SIMOTION D410 has completed its memory reset.

Note

Memory reset is cancelled if you do not return the DIL switch to MRES as specified within three seconds. Repeat the procedure in this case.

4.12.3Deleting user data from the CompactFlash Card

Overview

You can delete the user data using SIMOTION SCOUT. SIMOTION D410 must be operating in online mode. This deletes the following data:

User data from the "volatile data" area

Non-volatile data with the exception of IP and DP parameters

User data on the CompactFlash Card (user folders), including the SINAMICS configuration data

You can still go online to SIMOTION D410 at your programming device / PC. All licenses on the CompactFlash Card are retained.

D410

117

Commissioning Manual, 08/2008 Edition

Page 117
Image 117
Siemens D410 appendix Deleting user data from the CompactFlash Card, Switch position Mres