Commissioning (software) 4.6 Using drive-related I/Os by SIMOTION

Use of the onboard I/O by SIMOTION

For DI/DO channels, the terminal status of the output can be fetched back using the input (DI).

The 390 message frame transfers in PSD1 the control and status word of the control unit and in PSD2 the status of the onboard inputs/outputs.

For the 391 and 392 message frames, additional control and status information for the global measuring inputs is transferred. The content of these PSD3 to PSD15 is used exclusively by the measuring input technology object.

Table 4-3

D410 assignment of the addresses: Control/status word and onboard I/Os

 

 

 

 

 

PSD

Logical hardware address and bit number:

Input

Output

PSD1

Start address message frame 39x + 0

CU_ZSW

CU_STW

PSD2

Start address message frame 39x + 2, bit 0

DI 0

 

Start address message frame 39x + 2, bit 1

DI 1

 

Start address message frame 39x + 2, bit 2

DI 2

 

Start address message frame 39x + 2, bit 3

DI 3

 

Start address message frame 39x + 3, bit 0

DI 8

DO 8

 

Start address message frame 39x + 3, bit 1

DI 9

DO 9

 

Start address message frame 39x + 3, bit 2

DI 10

DO 10

 

Start address message frame 39x + 3, bit 3

DI 11

DO 11

PSD3

Start address message frame 39x + 4

Used internal for global measuring

 

 

inputs

 

 

 

(only for message frame 391, 392)

 

PSD4-7

Start address message frame 39x + +6

Used internal for global measuring

 

 

inputs 1 to 2

 

 

 

(only for message frame 391, 392)

 

PSD8-15

Start address message frame 39x + +10

Used internal for global measuring

 

 

input 3

 

 

 

(only for message frame 392)

 

To allow access by the I/Os to the individual PSDs, I/O variables must be created in SIMOTION. For this purpose, the input/output addresses displayed in the "PROFIBUS message frame" tab in the "SINAMICS Integrated - Configuration" dialog box are required.

The following figure shows an example of I/Os created in SCOUT: In this example, the start address of the 390 message frame for the input and output data is each 276.

Figure 4-20 Example: Access to message frame 390 using I/O variables.

D410

89

Commissioning Manual, 08/2008 Edition