Diagnostics data 6.1 Diagnostics by means of LED displays
Meaning | RDY | RUN/STOP | OUT > 5V | SF/BF: |
The upgrade/downgrade operation has completed | 2/1 | x | x | x |
(power OFF/ON of the upgraded/downgraded devices is | (yellow) |
|
|
|
necessary) |
|
|
|
|
STOP to RUN transition
STOP/STOPU
RUN to STOP transition
Memory reset requested by SIMOTION D410, or by means of mode selector switch.
Memory reset in progress
Memory reset completed
Firmware download to the integrated PROFINET interface is busy
Firmware download to the integrated PROFINET interface is completed SIMOTION cannot enter the RUN and Online mode
x
x
x
x
x x
0
1
(green)
2/1 | x | x |
(green) |
|
|
1 | x | x |
(yellow) |
|
|
2/1 | x | x |
(yellow) |
|
|
0,5/1 | x | x |
(yellow) |
|
|
0 | x | 0 |
1 | x | x |
(yellow) |
|
|
|
|
|
2/1 | x | 2/1 |
(yellow) |
| (yellow) |
1 | x | Λ |
(yellow) |
| (red) |
1)Priority of the displays: The displays always visualize the state which is assigned the numerically lowest priority level. The error of the next highest priority class is displayed after the cause of the previous signal state was eliminated.
The LED "OUT > 5V" display is controlled only by the encoder evaluation for the integrated X23 encoder interface in SINAMICS Integrated. The table below lists the display states and their meaning.
Table | LED display OUT > 5V | |
|
|
|
Status |
| Meaning |
0 |
| Electronic power supply is missing or outside the valid tolerance range. Power |
|
| supply ≤ 5 V. Use of an encoder with 5 V power supply. |
1 |
| Electronics power supply for measuring system available. Power supply >5 V. |
(yellow) |
| Caution: Always ensure that you can operate the encoder on the 24 V power |
|
| supply (e.g. HTL encoder). Operation of a 5 V encoder on the 24 V encoder |
|
| supply may lead to the destruction of its electronic components! This setting can |
|
| be selected in the expert list of the drive in parameter p405.1. |
D410 | 137 |
Commissioning Manual, 08/2008 Edition |