Commissioning (software)
4.12 Deleting data
D410
114 Commissioning Manual, 08/2008 Edition

Saving user data

The "Copy RAM to ROM" function is used in SIMOTION SCOUT to save the following data
from RAM to the CompactFlash card:
The technology data / user data from the "volatile data" area
Baud rate, PROFIBUS DP addresses, IP address, subnet mask and router address,
including the retain variables with their initial values from the "non-volatile data" area
Note
The "Copy RAM to ROM" command cannot be used to save the actual value of retain
variables to the CompactFlash Card.
Execute the "Copy RAM to ROM" function separately for SINAMICS Integrated. This
requires that the drive element has been selected in the Project Navigator.

See also

Properties of the user memories (Page 36)
4.12 Deleting data

4.12.1 Overview of data deletion

You can define the scope of data to be deleted from SIMOTION D410 memory described in
the "user memory concept". That is, you can choose to delete all data or only specific parts.
You have the following options of deleting data from SIMOTION D410:
Resetting the memory of SIMOTION D410
Deleting user data from the CompactFlash Card
Restoring the default settings of SINAMICS Integrated
Restoring the default settings of SIMOTION D410