Commissioning (software)

4.3 Configuring the system in online mode

D410
74 Commissioning Manual, 08/2008 Edition
4.3.2 Establishing the online connection
The procedure for an initial commissioning follows.
To perform an online configuration, you must establish an online connection to the
SIMOTION D410. In this case, no connection can yet be established to SINAMICS
Integrated. An appropriate message is output. Once the hardware configuration has been
loaded into the target device, an online connection to the SINAMICS Integrated is
established automatically. Proceed as follows:
1. Save and compile the project.
2. Establish an online connection.
3. Select the SIMOTION D410 device in the Project Navigator.
Note
Ensure that you use the "Download to the target device" function rather than "Download
to the target system". An automatic commissioning is no longer possible after "Download
to the target system". If "Download to the target system" has been used, "Restore factory
settings" must be performed on the drive element in order to start an automatic
commissioning afterwards.
4. Use the "Download to the target device" function to download the SIMOTION D410
device into the target device. The connection to SINAMICS Integrated is activated
automatically.
You can now run the automatic configuration at SINAMICS Integrated. For details, see
Section Starting automatic configuration (Page 75).
Additional references
Further information about establishing an online connection to the programming device / PC
is contained in the following documentation:
SIMOTION SCOUT
Configuration Manual
SIMOTION SCOUT
Online Help
In FAQ on the

"Utilities & Applications"

CD