Commissioning (software)

4.3 Configuring the system in online mode

4.3.2Establishing the online connection

The procedure for an initial commissioning follows.

To perform an online configuration, you must establish an online connection to the SIMOTION D410. In this case, no connection can yet be established to SINAMICS Integrated. An appropriate message is output. Once the hardware configuration has been loaded into the target device, an online connection to the SINAMICS Integrated is established automatically. Proceed as follows:

1.Save and compile the project.

2.Establish an online connection.

3.Select the SIMOTION D410 device in the Project Navigator.

Note

Ensure that you use the "Download to the target device" function rather than "Download to the target system". An automatic commissioning is no longer possible after "Download to the target system". If "Download to the target system" has been used, "Restore factory settings" must be performed on the drive element in order to start an automatic commissioning afterwards.

4.Use the "Download to the target device" function to download the SIMOTION D410 device into the target device. The connection to SINAMICS Integrated is activated automatically.

You can now run the automatic configuration at SINAMICS Integrated. For details, see Section Starting automatic configuration (Page 75).

Additional references

Further information about establishing an online connection to the programming device / PC is contained in the following documentation:

SIMOTION SCOUT Configuration Manual

SIMOTION SCOUT Online Help

In FAQ on the "Utilities & Applications" CD

74

D410

Commissioning Manual, 08/2008 Edition

Page 74
Image 74
Siemens D410 appendix Establishing the online connection, Additional references