Commissioning (software) 4.2 Configuring the system in offline mode

Figure 4-11 Configuration after HW Config alignment

Note

Repeat the HW Config alignment if the message frames for SINAMICS Integrated were changed. The addresses are not updated automatically.

4.2.5Downloading the project to SIMOTION D410

Procedure for downloading a project into the target system

1.Save and compile the project.

2.Go online to SIMOTION D410.

3.Select the "Download project to target system" command to download the project to SIMOTION D410. The connection to SINAMICS Integrated is activated automatically.

The drive has been assigned parameters and commissioned. You can now test the drive using the drive control panel.

Note

Online access to SINAMICS Integrated is not possible if HW Config is not loaded at the time you initially connect to the target system.

Download the data to HW Config in order to enable online access to SINAMICS Integrated.

D410

71

Commissioning Manual, 08/2008 Edition

Page 71
Image 71
Siemens appendix Downloading the project to Simotion D410, Procedure for downloading a project into the target system