2 Installing a BigIron RX-16 switch
Mounting a BigIron RX-16 chassis in a rack
Follow the steps given below to mount a BigIron
1.Determine the position of each chassis in the rack, for example, a chassis with the fewest modules on top, a chassis with more modules than the top chassis in the middle, and a fully populated chassis on the bottom.
2.Position the four screws for each chassis according to the spacings of the keyhole slots (the ones with the narrow portion pointing upwards) on the mounting brackets as shown in Figure 32. Do not secure the screws completely; leave approximately 1/4 inch of clearance between the back of the screw head and the rack.
FIGURE 31 Positioning the screws in a rack
5" | 3" |
1 | 2 |
1 | Unequal flange equipment rack | 2 | Network equipment rack |
3.Starting with the chassis that you want to mount in the lowest position in the rack, mount the chassis in the rack as shown in Figure 32. With two or more people lifting the chassis, slip the wide portion of each keyhole slot over the corresponding screw in the rack.
46 | Brocade BigIron RX Series Hardware Installation Guide |
|