Configuring the Thermal Profile for Fan Tray Operations (APX 8000)
Overview of the Thermal profile for fan tray operations
admin> write THERMAL written
admin> list [in THERMAL]
Related log messages
When the fan tray is in
LOG info, Shelf 1, Slot 42, Time:
Fantray now running in
LOG info, Shelf 1, Slot 42, Time:
Fantray now running at full speed (37 C)
If you modify the fan operation mode setting in the Thermal profile, the system generates an Info log message such as the following:
LOG info, Shelf 1, Slot 42, Time:
Fantray set to run in
Thermal alarms
When the temperature of the system reaches the
•The system generates an Error log message such as the following:
LOG error, Shelf 1, Slot 42, Time:
•The Alarm relay on the shelf controller is enabled. This turns on whatever signal is connected to the Alarm relay on the shelf controller.
•The Alarm status light in the fan tray front panel turns ON.
When the temperature falls back 2 degrees Celsius below the Alarm temperature trigger threshold, the alarm state is cleared and the following events occur:
•The system generates a Warning log message such as the following:
LOG warning, Shelf 1, Slot 42, Time:
•The Alarm relay on the shelf controller is disabled.
•The Alarm status light in the fan tray front panel turns OFF.
The