15.ABSOLUTE POSITION DETECTION SYSTEM

15.ABSOLUTE POSITION DETECTION SYSTEM

15.1Outline 15.1.1 Features

For normal operation, as shown below, the encoder consists of a detector designed to detect a position within one revolution and a cumulative revolution counter designed to detect the number of revolutions. The absolute position detection system always detects the absolute position of the machine and keeps it battery-backed, independently of whether the general-purpose programming controller power is on or off. Therefore, once the home position is defined at the time of machine installation, home position return is not needed when power is switched on thereafter.

If a power failure or a fault occurs, restoration is easy.

Also, the absolute position data, which is battery-backed by the super capacitor in the encoder, can be retained within the specified period (cumulative revolution counter value retaining time) if the cable is unplugged or broken.

General purpose programmable

Servo amplifier

controller

 

CPU

Changing the current position data

Positioning module

Pulse train

 

 

 

 

 

 

(command) Home position data

 

Current

 

EEPROM memory

 

Current

Position control

 

position

 

 

Speed control

 

LSO

 

position

data

 

 

 

1XO

 

data

 

 

 

I/O module

 

Backed up in the

 

 

 

 

Input

case of power failure

LS

 

1X

 

 

 

 

 

 

 

Detecting the

Detecting the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

number of

 

position within

 

 

 

 

 

 

revolutions

one revolution

 

 

 

Output

Battery

MR-BAT

 

 

 

 

 

 

 

 

 

 

 

 

Servo motor

 

 

 

 

 

 

 

 

1 pulse/rev Accumulative

 

 

 

High speed serial

 

revolution counter

 

 

 

 

 

Super capacitor

 

 

communication

 

 

 

 

 

Within-one-revolution counter

 

 

 

 

 

 

A, B, Z phase signals

 

 

 

 

 

 

(Position detector)

15.1.2 Restrictions

The absolute position detection system cannot be configured under the following conditions. Test operation cannot be performed in the absolute position detection system, either. To perform test operation, choose incremental in parameter No.1.

(1)Speed control mode, torque control mode.

(2)Control switch-over mode (position/speed, speed/torque, torque/speed).

(3)Stroke-less coordinate system, e.g. rotary shaft, infinitely long positioning.

(4)Changing of electronic gear after home position setting.

(5)Use of alarm code output.

15 - 1

Page 252
Image 252
Mitsubishi Electronics MR-J2S- A instruction manual Outline 15.1.1 Features, Restrictions, Cpu, Lso, 1XO