3. SIGNALS AND WIRING

(5)Torque limit

(a)Torque limit and generated torque

By setting parameter No. 28 (internal torque limit 1), torque is always limited to the maximum value during operation. A relationship between the limit value and servo motor-generated torque is shown below.

Max. torque

 

Generated torque

 

00

100

 

Torque limit value [%]

A relationship between the applied voltage of the analog torque limit (TLA) and the torque limit value of the servo motor is shown below. Generated torque limit values will vary about 5% relative to the voltage depending on products.

At the voltage of less than 0.05V, generated torque may vary as it may not be limited sufficiently. Therefore, use this function at the voltage of 0.05V or more.

[%]

100

 

 

 

Servo amplifier

value

 

 

 

 

TL

limit

 

5%

 

 

SG

Torque

 

 

2k

TLA

 

 

 

 

 

 

 

2k

P15R

 

 

 

 

 

 

0

0.05

 

 

 

 

0

10

Japan resistor

LG

 

 

 

 

 

 

TLA application voltage [V]

RRS10 or equivalent

SD

 

TLA application voltage vs.

 

 

 

 

torque limit value

 

 

 

(b)Torque limit value selection

Choose the torque limit made valid by the internal torque limit value 1 (parameter No. 28) using the external torque limit selection (TL) or the torque limit made valid by the analog torque limit (TLA) as indicated below.

When internal torque limit selection (TL1) is made usable by parameter No. 43 to 48, internal torque limit 2 (parameter No. 76) can be selected. However, if the parameter No. 28 value is less than the limit value selected by TL/TL1, the parameter No. 28 value is made valid.

(Note) External input signals

 

Torque limit value made valid

TL1

TL

 

 

 

 

0

0

Internal torque limit value 1 (parameter No. 28)

0

1

TLA

Parameter No. 28: Parameter No. 28

 

TLA

Parameter No. 28: TLA

 

 

 

1

0

Parameter No. 76

Parameter No. 28: Parameter No. 28

Parameter No. 76 Parameter No. 28: Parameter No. 76

 

 

1

1

TLA

Parameter No. 76: Parameter No. 76

 

TLA

Parameter No. 76: TLA

 

 

 

Note.0: TL/TL1-SG off (open)

1:TL/TL1-SG on (short)

(c)Limiting torque (TLC)

TLC-SG are connected when the torque generated by the servo motor reaches the torque set to internal torque limit value 1 or analog torque limit.

3 - 27