5. PARAMETERS

Class No. Symbol

60 LPF

Expansion parameters 2

61GD2B

62PG2B

63VG2B

64VICB

 

 

 

 

 

 

 

 

 

Name and function

 

 

 

Initial

Unit

Setting

Control

 

 

 

 

 

 

 

 

 

 

 

 

value

range

mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low-pass filter/adaptive vibration suppression control

 

 

 

0000

 

0000h

P S T

 

Used to set the low-pass filter and adaptive vibration suppression

 

 

to

 

 

control. (Refer to Chapter 8.)

 

 

 

 

 

1210h

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low-pass filter selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0: Valid

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1: Invalid

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When you choose "valid",

VG2 setting

 

[Hz]

 

 

 

 

 

 

 

 

 

 

 

 

 

2 (1 GD2 setting

0.1)

 

 

 

 

 

 

 

 

 

 

 

 

 

bandwidth filter is set automatically.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Adaptive vibration suppression control selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Choosing "valid" or "held" in adaptive vibration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

suppression control selection makes the machine

 

 

 

 

 

 

 

 

 

 

 

 

 

 

resonance control filter 1 (parameter No. 58) invalid.

 

 

 

 

 

 

 

 

 

 

 

 

 

0: Invalid

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1: Valid

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Machine resonance frequency is always detected

 

 

 

 

 

 

 

 

 

 

 

 

 

and the filter is generated in response to resonance to

 

 

 

 

 

 

 

 

 

 

 

 

 

suppress machine vibration.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2: Held

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The characteristics of the filter generated so far are held,

 

 

 

 

 

 

 

 

 

 

 

 

 

and detection of machine resonance is stopped.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Adaptive vibration suppression control sensitivity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Used to set the sensitivity of machine resonance detection.

 

 

 

 

 

 

 

 

 

 

 

 

 

0: Normal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1: Large sensitivity

 

 

 

 

 

 

 

Ratio of load inertia moment to servo motor inertia moment 2

 

70

0.1

0

P S

 

Used to set the ratio of load inertia moment to servo motor inertia

 

times

to

 

 

moment when gain changing is valid.

 

 

 

 

 

3000

 

Position control gain 2 changing ratio

 

 

 

100

%

10

P

 

Used to set the ratio of changing the position control gain 2 when

 

 

to

 

 

gain changing is valid.

 

 

 

 

 

200

 

 

Made valid when auto tuning is invalid.

 

 

 

 

 

 

 

Speed control gain 2 changing ratio

 

 

 

100

%

10

P S

 

Used to set the ratio of changing the speed control gain 2 when gain

 

 

to

 

 

changing is valid.

 

 

 

 

 

200

 

 

Made valid when auto tuning is invalid.

 

 

 

 

 

 

 

Speed integral compensation changing ratio

 

 

 

100

%

50

P S

 

Used to set the ratio of changing the speed integral compensation

 

 

to

 

 

when gain changing is valid. Made valid when auto tuning is invalid.

 

 

1000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5 - 22

Page 119
Image 119
Mitsubishi Electronics MR-J2S- A instruction manual LPF Expansion parameters 61 GD2B 62 PG2B 63 VG2B, Vicb