15.ABSOLUTE POSITION DETECTION SYSTEM

(2)Data set type home position return

Move the machine to the position where the home position is to be set by performing manual operation such as jog operation to turn the motor shaft more than one revolution. When the home position setting signal (CR) is on for longer than 20ms, the stop position is stored into the non-volatile memory as the home position ABS data.

The home position setting signal should be turned on after it has been confirmed that the in-position (D01 or INP) is on. If this condition is not satisfied, the home position setting warning (AL.96) will occur, but that warning will be reset automatically by making home position return correctly.

The number of home position setting times is limited to 1,000,000 times.

 

 

 

 

Manual feed (JOG, etc.)

 

 

 

 

(more than 1 revolution

 

 

 

 

of the motor shaft)

Servo Motor

 

 

 

 

 

 

 

 

 

 

Completion of

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

positioning

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(D01 or INP)

 

 

 

 

 

 

 

 

 

 

 

 

Home position

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

setting (CR)

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20 [ms] or more

Home position

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Update

ABS data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 