2. INSTALLATION

(2)Installation of two or more servo amplifiers

Leave a large clearance between the top of the servo amplifier and the internal surface of the control box, and install a fan to prevent the internal temperature of the control box from exceeding the environmental conditions.

Control box

100mm

 

(4.0 in.)

10mm

or more

Servo

(0.4 in.)

or more

amplifier

 

30mm

30mm

(1.2 in.)

(1.2 in.)

or more

or more

40mm

 

(1.6 in.)

 

or more

 

(3)Others

When using heat generating equipment such as the regenerative brake option, install them with full consideration of heat generation so that the servo amplifier is not affected.

Install the servo amplifier on a perpendicular wall in the correct vertical direction.

2.3 Keep out foreign materials

(1)When installing the unit in a control box, prevent drill chips and wire fragments from entering the servo amplifier.

(2)Prevent oil, water, metallic dust, etc. from entering the servo amplifier through openings in the control box or a fan installed on the ceiling.

(3)When installing the control box in a place where there are toxic gas, dirt and dust, provide positive pressure in the control box by forcing in clean air to prevent such materials from entering the control box.